9.4.2 Flow Conditions
Displays detailed blower and pump speed / valve
position readings that were recorded at the time the
fault occurred.
NOTE: If multiple units are connected to one thermostat, refer
to section 9.7.
FAULT FLOW CONDITIONS
LT1
LOW WATER TEMP
HEAT 1
11:11 AM 11/14
ECM TARGET CFM
ECM BLOWER RPM
FLOW RATE GPM
PUMP SPEED
VALVE POSITION
PREVIOUS
9.4.3 Input/Output Conditions
Displays the status of all physical and communicated
inputs, switches, and control outputs that were
recorded at the time the fault occurred.
NOTE: If multiple units are connected to one thermostat, refer
to section 9.7.
FAULT I / O CONDITIONS
LT1
LOW WATER TEMP
HEAT 1
11:11 AM 11/14
TSTAT
CONV COMM
Y1
Y1
Y2
Y2
W
W
O
O
G
G
H
H
OVR
DH
PREVIOUS
9.4.4 Confi guration Conditions
Displays the status of all dipswitch settings that were
recorded at the time the fault occurred.
NOTE: If multiple units are connected to one thermostat, refer
to section 9.7.
FAULT CONFG CONDITIONS
LT1
LOW WATER TEMP
HEAT 1
11:11 AM 11/14
S1
S2
1
ON
1
ON
2
ON
2
ON
3
ON
3
ON
4
ON
4
ON
5
ON
5
ON
6
ON
6
ON
7
ON
7
ON
8
ON
8
ON
PREVIOUS
14
SAFETY
OUTPT
HPS
LOC
CC
CO
RV
ACC1
OUTPT
ACC2
FAN
AL1
HWG
EH1
PUMP
EH2
S3
1
ON
2
OFF
3
OFF
4
OFF
LT1
WELL
LT2
WELL
G e o t h e r m a l H e a t P u m p S y s t e m s
9.4.5 Possible Causes
Possible causes as to why the fault occurred
NOTE: If multiple units are connected to one thermostat, refer
to section 9.7.
POSSIBLE FAULT CAUSES
LOW WATER COIL TEMP
LOW WATER TEMP - HTG
LOW WATER FLOW - HTG
800
LOW REFRIG CHARGE - HTG
550
INCORRECT LT1 SETTING
6.5
BAD LT1 THERMISTOR
60%
PREVIOUS
0%
9.5

CLEAR FAULT HISTORY

Clear Fault History will clear all fault codes stored in the
thermostat as well as the fault history in any connected
communicating controls (DXM2/AXM).
9.6
MULT-UNIT DIAGNOSTICS
If multiple units are connected to one thermostat when
Manual Operation, Control Diagnostics, or Dipstick
Confi guration is selected, the service personnel will see a
screen to select a specifi c unit by the last 4 digits of its serial
number.
NOTE: Multiple units may be connected directly to the ATC
thermostat or connected to one another in series, as shown by
the fi gure below.
Two
connections
on DXM2
board to allow
for multi-unit
installation
Or