AT C 3 2 U 0 1 C o m m u n i c a t i n g , P r o g r a m m a b l e T h e r m o s t a t - I O M
9.3
DIPSWITCH CONFIGURATION
Dipswitch Confi guration mode allows the service personnel
to view the status of all dipswitch settings for the connected
communicating control (DXM2/AXM) at the thermostat.
Navigate between confi guration screens using the left/right
arrow buttons.
NOTE 1: The unit control dipswitch settings cannot be
changed from the thermostat.
NOTE 2: If multiple units are connected to one thermostat,
refer to section 9.6.
CONTROL CONFIGURATION
DIPSWITCH S1
1
ON UPS ENABLED
2
ON DUAL COMP STG 1
3
ON HEAT PUMP TSTAT
4
ON RV O THERMOSTAT
5
ON DEHUMID OFF
6
ON EH2 AUX HEAT
7
ON BOILERLESS
8
ON SEE DXM2 AOM
PREVIOUS
CONTROL CONFIGURATION
DIPSWITCH S2
1
ON \ ACCESSORY 1
2
ON ACCESSORY 2
3
ON/
4
ON \ ACCESSORY 2
5
ON ACTIVE W/ COMP
6
ON /
7
ON H
DEHUM INPUT
8
ON FACTORY
SETTING
PREVIOUS
CONTROL CONFIGURATION
DIPSWITCH S3
1
ON
FACTORY
SETTING
2
OFF HWG TEST OFF
3
OFF HWG SP 125
4
OFF HWG DISABLED
JW3 LT1 SETTING WELL
PREVIOUS
9.4

FAULT HISTORY

Fault History mode displays the fi ve most recent stored fault
codes for the connected communicating control (DXM2).
Navigate between control fault codes using the up/down
arrow buttons. Press the center button to view more
information about the highlighted fault code.
NOTE: If multiple units are connected to one thermostat, refer
to section 9.7.
LT1 LOW WATER TEMP
NO FAULT
NO FAULT
NO FAULT
NO FAULT
PREVIOUS
NEXT
LT1 LOW WATER TEMP
HEAT 1 11:11 AM 11/14
FAULT TEMP CONDITIONS
FAULT FLOW CONDITIONS
FAULT I/O CONDITIONS
FAULT CONFIG COND
FAULT POSSIBLE CAUSES
PREVIOUS
9.4.1 Temperature Conditions
NEXT
Displays detailed temperature readings that were
recorded at the time the fault occurred.
NOTE: If multiple units are connected to one thermostat, refer
to section 9.6.
FAULT TEMPERATURE CONDITIONS
HEAT 1 11:11 AM 11/14
LT1
TEMP
LT2
TEMP
HOT WATER EWT
COMP DISCHARGE
LEAVING AIR
LEAVING WATER
ENTERING WATER
CONTROL VOLTAGE
PREVIOUS
TT038
SN - - - - - 0 1 2 3
LAST 5 FAULTS
FAULT CONDITION MENU
LT1 LOW WATER TEMP
R e v. : 4 F e b . , 2 0 1 3
NEXT
SELECT
SELECT
28.1
97.3
121.5
157.7
92.7
34.9
42.1
26.4
13