Basic Operation - Hsi Ignition Module; High Limits - Pentair Pool Products MiniMax NT Low NOx Series Operation & Installation Manual

Minimax nt low nox series pool & spa heaters
Table of Contents

Advertisement

Basic Operation
SAFETY CONTROLS, (cont'd.)
IGNITION MODULE
The Ignition Module is microprocessor based and operates on 24 VAC supplied by the transformer. The
control utilizes a microprocessor to continually and safely monitor, analyze, and control the proper operation
of the gas burners. The module with the presence of the flame sensor/ignitor or remote sensor, using flame
rectification, allows the heater to operate.

HIGH LIMITS

A "High Limit", is a safety device that opens the electrical circuit and shuts off the heater based on a
temperature set point within the "High Limit Device". The MiniMax NT Low NOx series of heaters
contains three (3) high limit devices, two (2) are located on the main inlet / outlet header, one sensing the
inlet water temperature and one sensing the outlet water temperature. The third high limit is located on the
exhaust outlet and senses the temperature of the flue gas.
OPERATION OF IGNITION MODULE
HEAT MODE
• When a call for heat is received from the thermostat supplying 24 VAC to the module terminal, the
control will perform a self check routine, for up to four seconds and begins the safety timing ignition
sequence. After the fan prepurge cycle, the hot surface ignitor is activated for a heat-up period followed
by energization of the gas valve for the trial for ignition period.
• When flame is detected during the trial for ignition, the ignitor is deactivated and the gas valve remains
energized. The thermostat and main burner flame are constantly monitored to assure the system
continues to operate properly. When the thermostat is satisfied and the demand for heat ends, the main
valve is de-energized immediately.
FAILURE TO LIGHT LOCK OUT
Should the main burners fail to light, or flame is not detected during the trial for ignition period of
(7) seconds, the ignition Module will stop the ignition sequence and the gas valve will be turned off.
The ignition module will go through this sequence three (3) times, if full ignition fails after the third try, the
module will go to full lock out. To restart the ignition sequence, turn the main electrical power off to the
heater, using the switch on the bottom of the junction box, for a period of one minute, then turn the power
back on, the heater will again try to light.
FLAME FAILURE—RE-IGNITION
If the established flame signal is lost while the burner is operating, the control will respond within 1 second.
The gas valve is de-energized and the control starts a new ignition sequence in an attempt to relight the
burner. If the burner does not relight, the control will go into lockout, requiring a manual reset.
P/N 472089
22
Rev. B 4-5-02

Advertisement

Table of Contents
loading

Table of Contents