Figure 1.3 Amx-Series Power Source - Front View - Pacific AMX series Operation Manual

Amx series ac power source
Table of Contents

Advertisement

SECTION 2 SPECIFICATIONS
2.1.1 INPUT POWER REQUIREMENTS
INPUT VOLTAGE
The Model 160-AMX accepts one of the following three phase input voltages:
1)
2)
3)
4)
5)
(cost option)
6)
INPUT CURRENT
The input current required by the Model 360-AMX at full rated load is stated below. Recommended input
service is also stated.
1)
2)
3)
4)
5)
(cost option)
6)
MODEL 160-AMX
208 VAC ∆ ±10%, 47-63 Hz
220 VAC ∆ ±10%, 47-63 Hz
240 VAC ∆ ±10%, 47-63 Hz
220/380 VAC ±10%, 47-63 Hz
240/416 VAC ±10%, 47-63 Hz
277/480 VAC ±10%, 47-63 Hz
V
in
208 VAC ∆
220 VAC ∆
240 VAC ∆
220/380 VAC
240/416 VAC
277/480 VAC
9A
(cont.)
(360-440 Hz cost option)
(360-440 Hz cost option)
(360-440 Hz cost option)
(360-440 Hz cost option)
(360-440 Hz cost option)
(360-440 Hz cost option)
INPUT CURRENT
31 A
; 40 A Service Recommended
rms
29 A
; 40 A Service Recommended
rms
27 A
; 40 A Service Recommended
rms
17 A
; 20 A Service Recommended
rms
16 A
; 20 A Service Recommended
rms
14 A
; 20 A Service Recommended
rms