Termination Resistor for XWEB300D
If XWEB300D is placed at the beginning or at the end of the line, please install its termination resistor by adding a jumper
in position 2 (JMP2 on the back side of the unit). Do not add the jumper if XWEB300D is placed in the middle of the RS485
line.
ZX CDU Connected to XWEB300D
ZX CDU connected to the Dixell XWEB300D with the Intelligent Store Solution Module using RS485 ModBUS.
Connect the ZX CDU to the ModBUS network as shown in Figure 9. Connect the network cable to the three-terminal
connector on the XWEB300D port that has been configured as ModBUS port (COM 12, 13, 14).
Connect port "13" of XWEB300D to port "D0" of Intelligent Store Solution Module and port "12" of XWEB300D to
port "D1" of Intelligent Store Solution Module for RS485 communication.
Figure 10. XWEB300D Connected to the Intelligent Store Solution Module
Dixell XWEB300D Configuration
XWEB300D is compatible with ZX CDU firmware version 2.1.1 plus patch "Update_CDU-UNITS_(20121203)".
Login into XWEB
Go to Information → Information
Check log update for "Update_CDU-UNITS_(20121203)". If this is not present, follow the steps below.
Open Dixell website http://www.dixell.com/xweb300d-xweb500-xweb500d/eng/, then login (register required)
Go to Support → System sw update → XWEB300D XWEB500 XWEB500D
Download the upgrade package
With your web-browser, login into XWEB
Go to Information → System Update menu
Provide the XW5 patch file
Once file has been selected wait until the upgrade procedure ends (XWEB reboots)
Verify the installation ended successfully by checking into the menu
Go to Information → Information for "Update_CDU-UNITS" string
Log in again and set up the ZX CDU
Go to Configuration → Devices drop-down menu
Go to Actions → New
Enter device name in the Name field (e.g. ZX CDU)
Select "ZXL-ECT_001" in the Model field
Enter the ModBUS address in the RS 485 address field
o
Refer to section "Dip Switch Address Settings"
Click New
Intelligent
Store Solution
Module
Dixell
XWEB
Shielded
Cable
Main Control
Board
13