Download Print this page

KING KBP2406 Installation & Maintenance Manual page 2

240v-1phase unit heater

Advertisement

King electrical mfg. company
Wiring Heater
WARNING - Before proceeding further
with the installation of this heater, turn off
the power and lock the supply line for the
heater at the main service box.
1. Remove wiring compartment cover.
2. Remove one of the knockouts from back of unit.
It is not necessary to remove grill covers.
3. Size service wire to adequately handle Amp load
of heater. Refer to the Circuit Sizing Table for
proper wire size and circuit protection.
4. Connect supply wire to L1 & L2 as shown in the
diagram below.
5. Secure power supply cable with clamps.
6. Connect groundwire to the green pigtail.
7. Reinstall wiring compartment cover.
8. Adjust the heater to the desired position.
INSTALLATION INSTRUCTIONS
This heater is shipped from the factory wired for
maximum wattage of 5700 Watts at 240 Volts.
To reduce the wattage unplug (disconnect) an
insulated push on terminal and wrap with electrical
tape to prevent the possibility of electrical contact
with other parts.
Field Wattage Selection
1. 5700 Watts factory wired
2. 4750 Watts disconnect terminal A
3. 3800 Watts disconnect terminals A,D
4. 2850 Watts disconnect terminals A,B,D
5. 1900 Watts disconnect terminals A,B,C,D
E - Black
Do Not Disconnect (Common)
F - Red
Do Not Disconnect
E Common
A
F
950
950
E Common
C
F
950
950
END VIEW OF ELEMENT SHOWING
QUICK CONNECT TERMINALS
1900•2850•3800•4750•5700
WATTAGES AVAILABLE IN ONE UNIT
Maintenance & Warranty Information:
The high quality and superior design of this heater will provide years of trouble-free performance. Each year
the heater should be checked and cleaned for lint and dust accumulation. We recommend using a soft bristle-
brush such as a paint brush to assist in removing contaminants from the heater. The motor is permanently lu-
bricated and does not need servicing. King Mfg. Company will repair or replace without charge any KBP2406
heater found to be defective or malfunctioning for five years after purchase to the original owner.
9131 - 10th Avenue South Seattle Washington 98108
WATTS BTUH VOLTS
1900
2850
3800
4750
5700
* Per the National Electric Code heating circuits are considered a continuous load and therefore must be derated
by 20%. For example: a 20 Amp heating circuit can not have more than 16 Amps of load connected. If heater is
operated at 208V it will draw 13% less Amps and produce 25% less wattage.
** Assumes an 8 ft. high ceiling; Use cubic feet to estimate wattage requirement when ceiling is not 8 ft.
*** If area is larger than 720 sq. ft. / 5,760 cubic feet use more than one heater.
A
ORANGE
F
RED
B
BLUE
Insulated Push on
Terminal
C
YELLOW
F
RED
D
GRAY
Insulated Push on
Terminal
BLACK #14
Thermostat
B
RED #14
950
OFF ....... L1-0, L2-0
FAN ....... L1-2, L2-4
HEAT...... L1-1, L2-4, L2-3
D
FAN DELAY
1-3 N.C., 1-2 N.O.
950
1-2 Closes on Temp Rise
Pic-A-Watt
Metal Sheath Element
CIRCUIT SIZING TABLE
AMPS
WIRE
SIZE
1-PHASE
6484
240
8
#14 / 2
9727
240
12
#14 / 2
240
16
#12 / 2
12969
16211
20
#10 / 2
240
19454
240
24
#10 / 2
950 WATT
950 WATT
950 WATT
950 WATT
950 WATT
950 WATT
FAN
DELAY
1
2
FAN
3
BLACK #16
PURPLE #16
GRAY #16
1
Rotary Switch
KBP2406
L1
240V -1ph
AREA COVERED
CIRCUIT
(sq. ft.** / cubic ft.***)
PROTECTION*
15A - 2P
240 / 1920
360 / 2880
15A - 2P
20A - 2P
480 / 3840
30A - 2P
600 / 4800
30A - 2P
720 / 5760
E
E
LIMIT
BLACK #16
ORANGE #14
2
3
4
A
B
L2
2007KBP2406.indd : 3/08

Advertisement

loading