Ariston G.C.N.:47-116-65 (24 kW) Installation And Servicing Instructions page 46

Condensing wall-hung gas boiler
Table of Contents

Advertisement

settings - adjustment - problem identifi cation menus
Description
6
3
DIAGNOSTICS
6
3
4
Zone 3 heat request
8
SERVICE PARAMETERS
8
1
BOILER STATISTICS
8
1
0
Number of hours burner operating in heater mode (xxh/10)
8
1
1
Number of hours burner operating in hot water mode (xxh/10)
8
1
2
Number of fl ame separations (nr/10)
8
1
3
Number of ignition cycles (nr/10)
8
1
4
Average length of heating request (minutes)
8
2
BOILER
8
2
1
Fan Status
8
2
2
Fan speed (x100) rpm
8
2
3
Circulation pump speed
8
2
4
Diverter valve position
8
2
5
D.H.W. Flow Rate (l/min)
8
2
8
Gas Power (kW)
8
3
BOILER TEMPERTURE
8
3
1
Heating fl ow temperature (in °C)
8
3
2
Heating backfl ow temperature (in °C)
8
4
SOLAR & STORAGE
8
4
2
Solar appliance water input temperature
8
5
SERVICE
8
5
0
Months to next maintenance
If setted the boiler will display that is time to call the installer for maintenance
8
5
1
Enable Maintenance advice
8
5
2
Maintenance Warning Reset
to erase the advice for maintenance
8
5
3
2nd Heat Exchanger Clogging State
8
5
4
PCB hardware version
8
5
5
PCB software version
8
6
ERROR LIST
8
6
0
10 last errors
This parameter allows the last 10 boiler errors fl agged to be displayed, indicating the day, month and year.
When the parameter is accessed, the errors are displayed listed from E00 to E99.
For each error, the following sequence is displayed:
E00 - error number
108 - error code
8
6
1
Error list reset
46
value
0 = OFF
1 = ON
0 = OFF
1 = ON
0 = OFF
1 = Low speed
2 = High speed
0 = D.H.W.
1 = Central Heating
from 0 to 60 (month)
0 = OFF
1 = ON
Reset? OK= Yes Esc = No
0 = DHW Exchanger OK
1 = Partially Clogged
2 = Very Clogged Please
Replace
from E00 to E99
Reset
OK = yes
ESC = no
activated only with the solar kit
connected