Enclosure: Plastic, dimensions 45 × 75 × 105 mm; degree of
protection IP 20
Mounting: Onto a standard mounting rail
Settings: Via drive interface (control panel)
Current Consumption: 65 mA at 24 V d.c.
Connectors:
• Light transmitter (grey) and receiver (blue) (Hewlett-Packard
Versatile Link) for connection to the drive
• One Combicon MVSTBW 2,5/8-ST-5,08 (8-pole, cross-section
2
2.5 mm
max.) screw terminal block for the fieldbus and power
supply:
X2
1
D(P)
D(P) = B = Data Positive (Conductor 1 in twisted pair)
2
D(N)
D(N) = A = Data Negative (Conductor 2 in twisted pair)
DG = Data Ground
3
DG
4
SHF
Cable screen AC earthing (via an RC filter)
5
SH
Cable screen earthing (directly earthed)
6
0V
Power supply for the module (24 V d.c. ± 10 %); screened cable.
7
+24 V
8
PE
Earth
General:
• All materials are UL/CSA approved
• Complies with EMC Standards EN 50081-2 and EN 50082-2
Appendix A – Technical Data