Fixing The Installation Plate - Samsung AVMWH020CA0 Installation Manual

System air conditioner
Hide thumbs Also See for AVMWH020CA0:
Table of Contents

Advertisement

Fixing the Installation Plate

020/026/032/035/040
Installation plate
Pipe hole
Ø
(
65mm)
(Unit : mm)
252
90
140
(Unit : mm)
052/070/072
Installation plate
Pipe hole
Ø
(
65mm)
(Unit : mm)
255
512
415
(Unit : mm)
8
E-
Before fixing the installation plate to a wall or window frame, you
must determine the position of the 65 mm hole through which the
cable, piping and hose pass to connect the indoor unit up to the
outdoor unit. When facing the air conditioner in position on the wall,
the piping and cable can be connected from the:
Right
Left
Underside;
Rear (right or left)
1
Determine the position of the pipe and drain hose hole using the right
figure and drill the hole with an inner diameter of 65 mm so that it slants
slightly downwards.
275
2
If you are fixing the indoor unit to a...
Wall
Window frame
3
Fix the installation plate to the wall in a manner appropriate to the weight
of the indoor unit.
If you are mounting the plate on a concrete wall with anchor
bolts, the anchor bolts must not project by more than 20 mm.
4
Determine the positions of the wooden uprights to be attached to the
window frame.
5
Attach the wooden uprights to the window frame in a manner appropriate
to the weight of the indoor unit.
6
Using tapped screws, attach the installation plate to the wooden uprights,
as illustrated in the last figure opposite.
325
052/070/072
Then follow Steps...