Amana GUI* Installation Instructions Manual page 15

Gas-fired warm air furnace
Table of Contents

Advertisement

A ground joint union, drip leg, and manual shutoff valve
must also be supplied by the installer. In some cases,
the installer may also need to supply a transition piece
from 1/2 inch to another pipe size.
Figure 15
Gas Inlet Through Furnace Left Side
(Upflow)
Figure 16
Gas Inlet Through Furnace Top Side
(Upflow)
The gas piping connections shown in Figures 13 and 14
are for a furnace equipped for a right hand discharge.
Adaptation for left hand discharge should be self
explanatory.
Figure 17
Horizontal Furnace
(Right Hand Discharge)
Counterflow Installations
When the gas piping enters through the left side of the
furnace, the installer must supply a straight pipe to reach
the exterior of the furnace (Figure 18).
Gas Inlet Through Left Side
(Counterflow)
A ground joint union, drip leg, and manual shutoff valve
must also be supplied by the installer. In some cases, the
installer may also need to supply a transition piece from 1/2"
to another pipe size.
When the gas piping enters through the right side of the
furnace, the installer must supply the following fittings
(starting at the gas valve):
• 90 degree elbow.
• Close nipple.
• 90 degree elbow.
• Straight pipe to reach exterior of furnace (Figure 19).
A ground joint union, drip leg, and manual shutoff valve
must also be supplied by the installer. In some cases, the
installer may also need to supply a transition piece from 1/2"
to another pipe size.
Gas Inlet Through Right Side (Counterflow)
"Left side" and "right side" above are as viewed for a
counterflow installation. Adaptation for horizontal airflow
should be self explanatory.
15
Figure 18
Figure 19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gci*Gui seriesGci series

Table of Contents