12.10. Indication Panel
LED
POWER
Color
Green
Light ON
Operation ON
Light OFF
Operation OFF
Note:
• If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation mode judgment, or
ON timer sampling.
• If Timer LED is blinking, there is an abnormality operation occurs.
• If e-ion LED is blinking, there is an abnormality of e-ion occurs.
• If PATROL LED is blinking, there is a gas sensor error detection.
12.11. Patrol Operation
A. Purpose
To monitor air dirtiness level by using gas sensor and activates e-ion operation whenever air is dirty.
B. Control Condition
a. Patrol operation start condition
• When the unit operation is started with "OFF/ON" button.
• When the unit stops, "Patrol" button is pressed, Patrol individual operation will start.
• During cooling only operation, "Patrol" button is pressed.
b. Patrol operation stop condition
When any of the following condition is fulfilled:
• When "OFF/ON" button is pressed.
• During any operation with Patrol, "Patrol" button is pressed again.
• When "e-ion" button is pressed.
• When OFF Timer activates.
TIMER
QUIET
Orange
Orange
Quiet Setting ON
Quiet Mode ON
Quiet Setting OFF
Quiet Mode OFF
POWERFUL
Orange
Powerful Mode ON
Powerful Mode OFF
50
e-ion
PATROL SENSOR
Blue
Blue
e-ion ON
PATROL ON
e-ion OFF
PATROL OFF