Dual input instructions

Complete the following steps to connect dual – 48 V dc power inputs to the power
supply terminals.
Note: For instructions on how to connect a single input to the terminal block, refer
1. Pull down on the terminal cover to open it.
2. Connect the protective ground wire to the protective ground terminal located in
3. Connect the first set of inputs to the A set of terminals as follows:
4. Connect the first set of inputs to the B set of terminals as follows:
5. Close the terminal block cover.

Disconnecting the DC Power Connection

The information in this section replaces the instructions for turning off the server
and disconnecting the power cable from the rear of the server in your xSeries
documentation.
Statement 19
CAUTION:
60
Hardware Maintenance Manual: xSeries 300
to "Single input instructions" on page 58.
the center of the terminal block.
Note: The wires must be connected in the order described to ensure the proper
operation of the – 48 V.
Return terminal
+
0 V ( )
a. Connect the return or 0 V wire to the A return (+) terminal on the terminal
block.
b. Connect the – 48 V (–) wire to the A (–) terminal on the terminal block.
a. Connect the return or 0 V wire to the B return (+) terminal on the terminal
block.
b. Connect the – 48 V (–) wire to the B (–) terminal on the terminal block.
Note: Torque the wiring-terminal screws to 12 inch-pounds (1.4
newton-meters).
Protective
ground terminal
Terminal block
cover
--
-48 V terminals ( )