OPERATION
4.4.2. Output Frequency Setting
Output frequency setting is possible for the range 0 to 400 Hz in increments
of 0.01 Hz.
4.4.3. Inverter Reset
Inverter can be reset via DeviceNet using Identity object reset service.
Note that this reset service also performs a parameter clear, the type of
which depends on the type of the Identity reset service.
4.4.4. Parameter Writing
For parameter writing, all standard, special and hidden parameters are
supported. In addition, the parameters listed in the Option-specific
Parameter section of this specification are supported.
4.5.
Output from Inverter to DeviceNet
4.5.1. Inverter Status
Inverter status can be monitored using class 0x2A, attribute 40, the A200E
Status. This is a bitmapped status byte defined as follows:
4.5.2. Inverter Monitoring
The following items can be monitored:
output frequency
output current
output voltage
running speed (RPM)
motor torque
bit
0
running
1
forward running
2
reverse running
3
up to frequency
4
overload
5
instantaneous power failure
6
frequency detection
7
alarm
definition
- 14 -
(RUN)
(SU)
(OL)
(IPF)
(FU)