Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor
Mitsubishi FX Series PLC Network
Communication Processor
BCNET-FX-S
User Manual
V1.0
www.wiseck.com

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi FX Series

  • Page 1 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor BCNET-FX-S Mitsubishi FX Series PLC Network Communication Processor User Manual V1.0 www.wiseck.com...
  • Page 3 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Table of contents One... BCNET-FX-S application..............................Product Overview...
  • Page 4 ..Turn on the power, watch the light............................ Connect to your computer, view Web pages........................Serial bus interface parameters...
  • Page 5: Product Overview

    ................................BCNET-FX-S application 1.1 product overview BCNET-FX-S is used in Mitsubishi FX1S/1n/2n/3s/3G/3GA/3GC/3U/3UC series, Huichuan, Shilin AX, Hehe Sichuan and Other PLC Ethernet data acquisition, very convenient to build production...
  • Page 6 PLC programming port, the upper computer through While Ethernet monitors PLC data, touch screen can communicate with PLC through multiplex interface x 2. BCNET-FX-S Support most SCADA software in industry control field, support Mitsubishi MC Ethernet protocol and MODBUSTCP two kinds of communication Way.
  • Page 7: Equipment Modification

    12, support the user side through Ethernet firmware updates, one-time purchase, permanent upgrade. 1.2.1 equipment modification Traditionally, the communication port of Mitsubishi FX Series PLC is usually equipped with a touch screen for monitoring PLC real-time data; and now, due to project requirements, the need to not affect the original...
  • Page 8 1.2.2 equipment informatization At present, the management of manufacturing enterprises is developing towards the direction of comprehensive information, and it is necessary to realize production management at the workshop level...
  • Page 9: Typical Applications

    Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor First of all, to build equipment information network, that is, equipment networking. For most production-oriented enterprises, they usually require: 1, equipment networking can not affect the existing production operation 2, the transformation of existing equipment less 3, networking time is short 4, Network communication stability, easy to maintain;...
  • Page 11: Hardware And Interfaces

    Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 2. Hardware and interfaces 2.1 hardware and interface diagrams...
  • Page 12: Installation

    24VDC power supply bus x 6. 2.3.1 Serial Interface X 1 X 1 is the MD8 bus port, which is directly connected to the communication port of Mitsubishi PLC through the communication line. The pin is defined as: 1 foot...
  • Page 14 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 2.3.2 serial interface x 2 The X 2 is the MD8 bus port, which connects directly to the touch screen's communication port through the communication line. The pin is defined as: 1 foot 2 feet 3 feet...
  • Page 15 2.3.5 WiFi Antenna X 5 X5 interface is BCNET-FX-S external WiFi antenna, using SMA interface with the external antenna, working frequency Should cover 2400-2500 mhz, antenna gain 7 db, 12 db, impedance 50 ω;...
  • Page 16 Twinkle 3. Get started with rapid application When you first get the BCNET-FX-S product, follow these steps to complete the initial testing of the product. 3.1 power on and observe indicator lights Power Mitsubishi Series PLC, connect communication line connecting PLC to COM1 port, the red PWR Power Indicator Light will be on...
  • Page 17 3.2 connect to your computer and view Web pages Connect the network card to the RJ45 port of BCNET-FX-S with an Ethernet cable (both cross and direct) BCNET-FX-S network port Link indicator should always be on. The Link light often lights up to indicate that BCNET-FX-S has established the ether...
  • Page 18 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Network connection. If your computer has a wireless card enabled, disable the wireless card (which sometimes affects the communication of the cable card) . Set the IP of your computer's local network card to 192.168.1.100. As shown below: Run Internet Explorer on your computer and type: 192.168.1.188 in the address bar (this is BCNET-FX-S...
  • Page 20 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Equipment basic information: pre-set by the factory. Serial interface parameters and status: display the current module and PLC connection status, display the current module and HMI connection status. Ethernet interface parameters and status: displays the IP address, subnet mask, and gateway address of the current port, and displays the current TCP server port number.
  • Page 21 Eleven...
  • Page 22 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 3.2.1 serial bus interface parameters Automatic identification of PLC model: the default is“Open”, “Open” state does not need to set the“PLC model selection”, will be from Moving Recognition PLC model. Automatic identification HMI parameters: the default is“On”, “On” state does not need to set the“HMI baud rate selection”, will automatically identify the HMI baud rate.
  • Page 23 Twelve...
  • Page 24: Ethernet Interface Parameters

    Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 3.2.2 Ethernet interface parameters Basic settings: Set BCNET-FX-S IP address, mask and gateway; MC Server Port Number: Defaults to 5551, which is used for MCTCP protocol communication and GX WORK2, GX Developer Programming software used for programming.
  • Page 25 Thirteen...
  • Page 26 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 3.2.3wifi interface parameters Station (module connection hotspots) : This setting, the module as a client to connect WiFi hotspots; Station function: if the Station function is enabled, the connection hotspot function will not be enabled if the Station function is turned off.
  • Page 27 Create hotspot SSID: the name of the AP hotspot SSID created by the module, up to 32 characters.
  • Page 28: Communications Diagnostics

    Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Create Hot Password: module to create the AP Hot Password, up to 64 characters. Create hotspot encryption mode: module to create the AP hotspot encryption mode, support no password, WEP, WPA and WPA2 mode. IP address of the AP: IP address of the AP hotspot, default 192.168.3.1.
  • Page 29 Fifteen...
  • Page 30 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor HMI-> total number of communication requests: number of all communication requests sent to the touch screen; number of correct responses: number of correct touch screen responses to these requests; number of false responses: number of false touch screen responses;...
  • Page 31 Sixteen...
  • Page 32: Set The Ip Address

    Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 3.3 BC device configuration module 3.3.1 search device Run the BCDEVICE software, as shown below: 1. Before searching for devices, please select the computer that connects BCNET-FX-S module [ network interface ] ; if the computer and the module are connected by network cable, please select [ local connection ] ;...
  • Page 33 After the modification, click the [ settings ] button to save the parameters. Seventeen...
  • Page 34 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 3.3.3 modification of equipment parameters Under normal circumstances, the BCNET-FX-S module does not need to modify the parameters of the normal communication has been. 1. Click the“Modify device parameters” button, in the pop-up dialog box, you can view the“Serial interface parameters configuration”...
  • Page 35 Eighteen...
  • Page 36 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Automatic Identification PLC model: recommended to open, so that the BCNet module can automatically get the PLC model, and match the communication parameters Number. PLC model selection: when the automatic identification of the PLC model closed, you can manually select the PLC type.
  • Page 37 Nineteen...
  • Page 38 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Feature selection: default for HMI communications. Parameter self-adaptation: HMI communication parameter self-adaptation, can automatically identify HMI touch screen communication parameters; baud rate: current baud rate for HMI communications, optional 9600,19200,38400,57600, and 115200 bps. Click on the“Network interface parameters configuration”...
  • Page 39 Twenty...
  • Page 40 Subnet Mask: The Module's subnet mask address, the initial value of 255.255.255.0; Gateway address: the module's gateway address, the initial value is 192.168.1.1; B)[ server port ] Mitsubishi MC Protocol Port Number: Mitsubishi MCTCP protocol (MC1E frame binary) access module port number, default 5551;...
  • Page 41 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor MODBUSTCP port number: the port number when accessing the module using the MODBUSTCP protocol, default 502; C) Web options Disable Web page configuration: If Disabled, you will not be able to access the module's internal Web pages through Internet Explorer, and you will not be able to configure the module through the Web page Block parameters;...
  • Page 42 Twenty-two...
  • Page 43 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Enable AP function: enable AP function, create hot spots; Create hotspot name: module creates the SSID name of the AP hotspot, maximum support 32 characters; Create Hot Password: module to create Ap Hot Password, the maximum support of 64 characters;...
  • Page 45 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Enable Station function: enable Station function, connect hot spots; The name of the hotspot to be connected: the SSID name of the AP hotspot to be connected by the module, which can support up to 32 characters; Hot password to connect: module to connect the AP Hot Password, the maximum support of 64 characters;...
  • Page 46 A)[ diagnostic information ] Twenty-four...
  • Page 47 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor The diagnosis information is divided into serial bus (PLC) , extended bus (HMI) , network interface information and system operation information Serial Bus -LRB-PLC) : can view the current connection parameters and status of the module PLC PLC, can view the total number of communication requests, correct Response Times and error response times;...
  • Page 48 Twenty-five...
  • Page 49: Communication Test

    Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor The state of the WiFi interface is divided into AP (module as hotspot) and Station (module connection hotspot) AP (module as a hotspot) : Can View the module as the current AP hot operating parameters and status;...
  • Page 51 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 4.wi-fi application guide BCNET-FX-S integrated WiFi function, BCNet-FX-S can achieve AP + STATION mode of work, the following are introduced This paper introduces the module as the configuration and application of AP hotspot and Station mode.
  • Page 52 Twenty-seven...
  • Page 53 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Click scan current hot spot, wait for the scan to complete, select the hot spot to connect, type the connection password, click select the hot spot; After you perform the previous step, the hotspot name to connect, hotspot password to connect, and hotspot authentication method are automatically populated, the IP address, subnet mask, and gateway address are configured in module Station mode if“Auto-fetch.”...
  • Page 54 Twenty-eight...
  • Page 55 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Set to off, the set static IP address, subnet mask, and gateway address are used; Once you have determined that the parameters are correct, click download parameters: Twenty-nine...
  • Page 56 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 4.1.2station application 1. After the module is properly connected to the AP hotspot, make sure that the computer and the module are in the same AP hotspot or LAN; run at this time BCDEVICE searches;...
  • Page 57 Thirty...
  • Page 58 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor At this time, the IP address of the communication test is 192.168.1.135, which is the IP address of the module as the Station mode Parameter configuration and diagnostics through BCDevice At this point through the BCDEVICE module parameters can be configured and diagnosed, the above figure describes the“Device operation diagnosis”...
  • Page 60 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor GX Work2 goes through“EthernetBoard”> > “PLC Module” and fills in the IP address of the Module when it is doing a Station “192.168.1.135”, click“Communication test” to prompt“Successfully connected to FX3G/FX3GCCPU”. Configuration software connection configuration Software Connection please refer to the specific“5.SCADA communication”, the corresponding configuration software to connect the device IP address, fill in...
  • Page 61 Thirty-two...
  • Page 62 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 2. In the“AP (module as Hot)” interface check the“Enable AP function, create hot”; The configuration of specific AP hotspots is shown below:...
  • Page 63 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor A) modify“Create hotspot name”, which defaults to“BCNET-FX-S: XXXXXX”, where“XXXXXX” is the product Serial number of the product; B) in“Create hotspot password”, enter the hotspot connection password, factory default password“12345678”, password length at least Characters;...
  • Page 65 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 4.2.2AP applications 1. Laptop Open Wireless Network card, search for hot spots to find“BCNET-FX-S: XXXXXX”, type hot password, proceed Connection; Thirty-five...
  • Page 66 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor After the laptop connected to the“BCNET-FX-S: XXXXXX” hotspot successfully, as shown below, BCNet assigned 192.168.3.100 IP addresses to the laptop, and the module as the hotspot's IP address was 192.168.3.1; First, Ping the IP address of the module as a hotspot to see if the network link is established successfully,...
  • Page 68 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor The Computer Can Ping Pass 192.168.3.1, indicating that the laptop through wireless network card and BCNET-FX-S to establish a network connection; At this time the computer can 192.168.3.1 data acquisition and programming operations, the IP address is the IP address after the PLC to WiFi hot spots;...
  • Page 69 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor B) parameter configuration and diagnostics via BCDEVICE At this point through the BCDEVICE module parameters can be configured and diagnosed, the above figure describes the“Device operation diagnosis” bound Below, “View current connected devices”, you can see that only one Station device connection currently exists, and modules are assigned to It has an IP address of 192.168.3.100 and a connection signal strength of -53 DBM to the Station;...
  • Page 70 Thirty-eight...
  • Page 71 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Configuration software connection configuration Software Connection please refer to the specific“5.SCADA communication”, the corresponding configuration software to connect the device IP address, fill in Write the module as the IP address of AP; Thirty-nine...
  • Page 72 Mitsubishi to Ethernet protocol connection. 5.1 BCNet-FX-S connection programming software BCNET-FX-S support Mitsubishi Programming Software GX Works2 through the Ethernet FX series of PLC Program Download and monitor functions. There are three ways to use GX Works2 programming software, as follows: The first method is suitable for FX3G/3GC, FX3S, FX3U/3UC;...
  • Page 73 2. After the pop-up, double-click the“Ethernet board” option on the computer side, then click“Yes” in the reminder; Double-click“PLC Module” on the programmable controller side; Forty...
  • Page 74 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 3. In the settings that pop up later, click“Search for FXCPU (S) on the network” and it will search for BCNET-FX-S The connected FX3UC. Click on the label in the diagram to select the last click to confirm;...
  • Page 76 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 5. Then you can"On-line" option bar, PLC Reading, writing and monitoring and other operations. Forty-two...
  • Page 77 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 5.1.2 is suitable for FX1N/1NC, FX2N/2NC, FX1S, FX3G/3GS, FX3S, FX2N/2NC FX3U/3UC Mode two applies to the full range of FXCPU, choose this mode mainly for FX1N, FX2N, FX1S series PLC used. The implementation of GX Works2 Ethernet connection FX2NC through BCNet-FX-S for example, to illustrate the use of steps: 1.
  • Page 79 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 3. In the subsequent pop-up setup, enter the IP address of BCNET-FX-S in the IP address and the port number The port number of BCNET-FX-S. Click on the label in the diagram, then click“Confirm”; Four.
  • Page 80 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 5. Then you can"On-line" option bar, PLC Reading, writing and monitoring and other operations. 5.1.3 applies to FX3U/3UC The third method is suitable for FX3U/FX3UC, this time through BCNET-FX-S GX Works2 Ethernet connection FX3UC For example, explain the steps to use: Forty-five...
  • Page 81 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 1. Create a new FX3U/FX3UC project and double-click the Connection target in the navigation bar: Connection. 2. After popping out of the palette, select the“Ethernet board” option on the computer side and then click yes in the reminder On the programmable controller side, double-click“Ethernet module”;...
  • Page 83 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Four. Select the IP address in the above, click on the“Communication Test”, you can prompt and FX3UCCPU connection success. 5. Then you can"On-line" option bar, PLC Reading, writing and monitoring and other operations. Forty-seven...
  • Page 84 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 5.2bcnet-fx-s connection kingview 1. Build new projects and open them. 2. Click“COM1”, select“New”, select“FX3U” in the dialog box that pops up, click“Under” One Step”. 3. Enter the logical name of the device and click“Next”. Forty-eight...
  • Page 85 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Four. Enter the IP address of BCNET-FX-S and PLC port number 5551. 5. Enter the communication parameters, the default can be, and then click“Done”. Forty-nine...
  • Page 86 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Fifty...
  • Page 87 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 5.3bcnet-fx-s connects to MCGS 1. Open Kunlun Tongtai MCGS configuration environment-device window, device management to add“Universal TCP/IP parent device” and“Mitsubishi Q Series TCPIP.
  • Page 88 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 2. Double-click“Universal TCP/IP parent device 0-[ universal TCP/IP parent device ]”, select the correct“Network type” as“1-TCP”, fill in the monitoring computer's IP address in the“Local IP address”, in“Remote IP address” fill in the BCNET-FX-S module's IP address, “Remote port number”...
  • Page 89 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 3. Double-click“Device 0-[ Mitsubishi Q Series TCPIP ]”, the default parameter can be, click to confirm. 5.4bcnet-fx-s connection force control 1. Open the power control development system, double-click“IO device configuration” and...
  • Page 90 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 2. To create a new device, type“Device name” and click“Next”. 3. Enter the IP address of the BCNET-FX-S module in“Device IP address” and 5551 in“Port”. Click next.
  • Page 91 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Four. “Device type” select“BINARY” and click finish. 5.5bcnet-fx-s connects to Kepware OPC 1. Open the KEPSERVEREX software, Click“Click to add a channel”, create a new channel, enter a channel name, and Click“Next”. Fifty-five...
  • Page 92 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 2. Select the“Mitsubishi Ethernet” driver and click“Next”. 3. Network card settings, select“Default”, click next, other parameters Default, until complete.
  • Page 93 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Click to add a device to create a new device. Enter the device name and click next. Select the correct PLC model and click next.
  • Page 94 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 6. Input Module IP address: 255, where 255 as the default parameters, click next, other parameters default. Seven. IP select“TCP/IP”, port number input: 5551, click next, until complete.
  • Page 95 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 5.6bcnet-fx-s connects to WINCC 1. New project, right-click“Variable management”, click“Add new driver”.
  • Page 96 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 2. Select“Misubishi Ethernet.chn”. 3. Right-click“Mitsubishi FX3U series” and click“New driver connection”.
  • Page 97 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor Four. Click on“Properties”, fill in the IP address of the module, the default port number is“5551”, the protocol select“TCP”, the default PC number is“255”, click on“OK”.
  • Page 98: Modbustcp Communications

    Can directly access the Mitsubishi FX Series PLC Internal Data Area, Modbus protocol address in the BCNet internal Has been mapped to the default FX Series PLC address area, the implementation of the function numbers include: FC1, FC2, FC3, FC5, FC6 and FC16.
  • Page 99 XM = 100001 + FC2(read Dec (m) 100,001 Enter: X 0ー input) 位 ③ 2000 TM = 400001 + 400,001 Timer: T 0 CM = 401001 + 401001 Counter: C 0 FC3(read CM = 401201 + register) FC3:125 Counter: C200 (M-200) * 2 FC16(write 401201...
  • Page 100 ID is PLC (for example 1) , Select 03: Holding Register, Address = 1301, Length = 100. The sub-window data area displays the hexadecimal data of 401301-401400, which corresponds to the values of the special register D8000 to D8100 of the Mitsubishi FX Series PLC, as shown in Figure 2.
  • Page 102 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 图 2 Double-click the data in the child window data area to modify the value. 6.1 WINCC connects to BCNET-FX-S via MODBUSTCP driver 1. Open the WINCC software, create a new project, right-click“Variable management”, select“Add new driver connection”, select“Modbus TCPIP.chn”...
  • Page 103 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 3. Right-click“Variable name”, create a new variable, here we create a new d 0 variable, the corresponding address settings please click“Select”, Pop-up dialog box, “Area” select“4x hold register”, “4x” fill in“402001”.
  • Page 104: Product Specifications

    Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 6. Product specifications Model BCNET-FX-S Mitsubishi FX Series PLC Ethernet Communication Processor Description Color Metal Black PWR, COM1, COM2, WiFi Status display Link/Active indicator, automatic polarity cross Ethernet interface Interface type...
  • Page 105 BCNET-FX-S Ethernet Manual BEICHEN Automation communication processor WINCC, Kunlun general state, King of configuration, force control, Configuration software Jie control, IFIX, INTOUCH and so on OPC software Kepware OPC Diagnostic and parameter setter Internet Explorer, default 192.168.1.188, BCDEVICE 具 FX programming port Power Supply Mode power/external connection 24V 24VDC/100mA...
  • Page 107 Use the manual Beichen Automation BCNET-FX-S Ethernet communication processor 7. Contact us Name: Wuxi Beichen Automation Co. , Ltd. Address: 1501,1503, Block A, creative garden, 100 di Cui Road, Liyuan Development Zone, Wuxi City, Jiangsu Province Postcode: 214072 Sales: 0510-85136823,0510-85166823 Technical Support: 0510-85162669,85166813 Website: www.beichen-automation.com Wechat public ID:...