Maintenance Schedule
SECTION XVI - Maintenance
Procedures

MAINTENANCE PROCEDURES

WARNING
The
PERFORMANCE
inspected and serviced annually, prefer-
ably at the start of the heating season, by
a qualified service technician. In addi-
tion, the maintenance and care of the
unit as outlined on page 60 and further
explained on pages 61 through 64 should
be performed to assure maximum effi-
ciency and reliability of the unit. Failure
to service and maintain the PERFOR-
MANCE and the system components
could result in equipment failure, caus-
ing possible severe personal injury,
death or substantial property damage.
NOTICE
The following information provides
detailed instruction for completing the
maintenance items outline in the mainte-
nance schedule on page 60. In addition
to this maintenance, the PERFOR-
MANCE should be serviced at the begin-
ning of the heating season by a qualified
service technician.

Reported Problems

Any problems reported by the owner
should be checked, verified and corrected
before proceeding with any maintenance
procedures.
Check the Surrounding Area
Verify that the area surrounding the PER-
FORMANCE is free of combustible / flam-
mable materials or flammable vapors or
liquids. Remove immediately if found.
is free of any contaminates. Refer to the list of
potential materials listed on page 7 of this
manual. If any of these products are in the
room from which the unit takes its com-
bustion air, they must be removed immedi-
ately or the combustion air intake must be
relocated to another area.
Inspect the Burner Area
Remove the burner hood and inspect the
should
be
appearance of the burner components.
Vacuum any dirt or debris from the burner
components.
Remove the venturi inlet elbow to check for
dirt and debris. Remove any obstructions.
WARNING
Do not use solvents to clean any of the
burner components.
could be damaged, resulting in unreli-
able or unsafe operation.
Check System (Primary and Domestic)
Piping
Inspect all piping on the Primary Heating
system and the Domestic system for leaks
and verify that the piping is leak free.
Inspect the fittings and components on the
unit and verify they are leak free.
WARNING
Eliminate all primary water system leaks.
Continual fresh make-up water will
reduce the outer tank life causing tank
failure. Leaking water may also cause
severe property damage to the surround-
ing area.
61