Use Of Antifreeze In The Primary System; Filling The Inner (Domestic) Tank And System; Filling The Outer (Primary) Tank And System - Delta Performance PG-25 Installation And Maintenance Manual

Performance series gas fired combination heaters
Table of Contents

Advertisement

Start-Up Preparation
NOTICE
System water, including additives must be
practically non-toxic, having a toxicity
rating or Class of 1, as listed in Clinical
Toxicology of Commercial Products.

Use of Antifreeze in the Primary System

WARNING
NEVER use automotive or ethylene gly-
col antifreeze or undiluted antifreeze in
the primary system as freeze protection.
This can cause severe personal injury,
death or substantial property damage if
ignored.
Determine the antifreeze fluid quantity
using the system water content volume and
following the antifreeze manufacturer
instructions.
The primary outer tank volume of the PER-
FORMANCE is 20 gallons. Remember to
include the volume of the expansion tank.
Check with local codes requirements for
the installation of back flow preventers or
actual disconnect from the make up water
supply line.
Ensure the concentration of antifreeze to
water does not exceed a 50/50 ratio.
NOTICE
System water including additives must be
practically non-toxic, having a toxicity
rating or Class of 1, as listed in Clinical
Toxicology of Commercial Products.
Filling the Inner (Domestic) Tank and
System
WARNING
Proceed with filling instructions for the
inner and outer tanks only after ensur-
ing the water meets the requirements
listed in this installation manual. Failure
to comply could result in damage and
improper operation of the unit.
CAUTION
Never operate the PERFORMANCE
unless both the inner and outer tanks are
completely filled.
CAUTION
Always fill the inner tank prior to filling
and pressurizing the outer tank. Failure
to properly fill the inner tank could
result in damage to the inner tank.
1. Ensure the domestic drain valve is closed.
2. Open the isolation valves on the domestic
cold supply piping to the PERFOR-
MANCE and on the domestic hot outlet
piping to the building (if provided).
3. Vent any air from the domestic piping sys-
tem by opening faucets near the unit.
Continue filling the domestic system until
there is a constant flow of water from the
faucets.
4. Close the hot water faucets.
Filling the Outer (Primary) Tank and
System
1. Close the primary drain valve located on
the rear of the unit and any manual or auto-
matic air vent in the system.
2. Open all system isolation valves.
50