Section Ii - Combustion Air And Venting; Combustion Air Contamination - Delta Performance PG-25 Installation And Maintenance Manual

Performance series gas fired combination heaters
Table of Contents

Advertisement

Combustion Air and Venting
SECTION II - Combustion Air and
Venting

Combustion Air Contamination

WARNING
If the PERFORMANCE combustion air
inlet is located in any area likely to cause
or contain contamination, or if products,
which would contaminate the air cannot
be removed, the combustion air must be
repiped and terminated to an outside
location. Contaminated combustion air
will damage the unit and its burner sys-
tem, resulting in possible severe personal
injury, death or substantial property
damage.
WARNING
Do not operate a PERFORMANCE if its
combustion air inlet is taken inside in a
laundry room or pool facility.
areas will always contain hazardous con-
taminants.
Pool chemicals, laundry products, com-
mon household cleaners and hobby
products often contain fluorine or chlo-
rine compounds. When these chemicals
pass through the burner and vent sys-
tem, they can form strong acids. These
acids can create corrosion of the outer
tank, burner components and vent sys-
tem, causing serious damage and pre-
senting a possible threat of flue gas
spillage or water leakage into the sur-
rounding area.
Please read the information listed below.
If contaminating chemicals are located
near the location of the combustion air
inlet, the installer should pipe the com-
bustion air inlet to an outside area per
SECTION VI of this installation manual.
Potential contaminating products
-
Spray cans containing chloro/fluorocar-
bons
-
Permanent Wave Solutions
-
Chlorinated wax
-
Chlorine - based swimming pool chem-
icals / cleaners
-
Calcium Chloride used for thawing ice
-
Sodium Chloride used for water soften-
ing
-
Refrigerant leaks
-
Paint or varnish removers
-
Hydrochloric acid / muriatic acid
-
Cements and glues
-
Antistatic fabric softeners used in
clothes dryers
-
Chlorine-type bleaches, detergents, and
cleaning solvents found in household
laundry rooms
These
-
Adhesives used to fasten building prod-
ucts and other similar products
Areas likely to contain these products
-
Dry cleaning / laundry areas and estab-
lishments
-
Beauty salons
-
Metal fabrication shops
-
Swimming pools and health spas
-
Refrigeration Repair shops
-
Photo processing plants
-
Auto body shops
-
Plastic manufacturing plants
-
Furniture refinishing areas and estab-
lishments
-
New building construction
-
Remodeling areas
-
Garages with workshops