Sample Wiring Configurations

The next several pages provide sample Thermostat connections and configurations for
your reference.
WARNING! Do not install LINE VOLTAGE wires to a LOW VOLTAGE wire.
IMPORTANT! When utilizing power stealing, Control4 recommends installing the
included 270 Ohm bypass resistor on the HVAC system to minimize any potential
side effects. See the previous section "Installing a Bypass Resistor to Enable Power
Stealing on a Wireless Thermostat."
IMPORTANT! Do not install any Remote Temperature Sensors to the TS terminals
other than supported external temperature sensors (Flush Mount Remote Tempera-
ture Sensor, Aprilaire™ Model 8051 or Duct/Outdoor Remote Temperature Sensor,
Aprilaire Model 8052, etc.). For installation instructions, see your Aprilaire docu-
mentation.
IMPORTANT! Install the U-shaped Terminal jumper wire between RC and RH for a
single stage system.