to 2 degrees, the heating system will engage until reaching 70 degrees Fahrenheit.
Cooling Cutoff Point: Sets the temperature for the cooling system to turn off past the setpoint.
To adjust, use the up and down arrows and press Set Cool Cutoff to confirm the change.
Example: If the Cool Point is set to 68 degrees Fahrenheit, and the Cooling Cutoff Point is set to
2 degrees, the cooling system will engage until reaching 66 degrees Fahrenheit.
Stage Minimum Off Time (Minutes): Sets the minimum time heating or cooling will remain off
before initiating again. To adjust, use the up and down arrows. The setting takes affect when
you close this box. Example: If while cooling or heating, the temperature does not reach the
designated Cutoff Point before the Maximum Run Time is reached, the cooling system will shut
off and not initiate cooling again until the Minimum Off Time is reached.
NOTE: Some HVAC systems automatically enforce a minimum off time. In this case,
the heating or cooling will remain off for the higher of the two settings
(Thermostat or HVAC system).
Stage Configuration (Heat 1-2, Cool 1-2, Auxiliary Heat, Emergency Heat)
The following settings take affect when you close the page.
NOTE: Auxiliary heat and emergency heat are for heat pump systems only.
Delta: Sets how many degrees the current temperature will reach beyond the temperature set
point before the stage engages. To adjust, use the up and down arrows. Example: If the Heat
Set Point is 70 degrees Fahrenheit, and the delta is 2 degrees, the heat stage will engage when
the temperature reaches 68 degrees Fahrenheit.