Connector Modifications
Compression Lugs
Table P2-13 – Lugs
Style
Amp Rating
125
250
MLO
400
600
100
225
Main Breaker
400
600
Table P2-14 – Alternate Lugs*
Style
Amp Rating
MLO
400
Main Breaker
400
*Contact local Siemens representative for any modifications.
Breaker Type
Compression Connectors
N/A
(1)#6 - 350 Kcmil Al/Cu
N/A
(1)#6 - 350 Kcmil Al/Cu
N/A
(1) 400 - 600 Kcmil Cu or
(2)#6 - 350 Kcmil Al/Cu
N/A
(2)#6 - 350 Kcmil Cu or Cu/Al or
400 - 600 Kcmil Al/Cu
ED4, ED6, HED4
(1)#14-2/0 AWG Cu or Al
CED6
QJ2, QJH2, QJ2H
(1)#6 AWG - 350 Kcmil Cu or Al
FXD6, HFD6, CFD6
(1)#6 AWG - 350 Kcmil Cu or Al
JD6, JXD6, HJD6,
(2)#1/0 AWG - 500 Kcmil Cu or Al
CJD6, SJD6, SHJD6,
SCJD6
LD6, LXD6, HLD6,
(2)#2/0 AWG - 500 Kcmil Cu or Al
CJD6, SLD6, SHLD6,
SCLD6
Breaker Type
Compression Connectors
N/A
(1) 250 - 750 Kcmil or
(2)#3/0 AWG - 250 Kcmil Cu or Al
JD6, JXD6, HJD6,
CJD6, SJD6, SHJD6,
(1)#4/0 AWG - 750 Kcmil Cu or Al
SCJD6
Box Height Addition
6
6
6
6
Box must go to 24" wide on CED6 breaker only
Add 6" to box height for NØ
Box must go to 24" wide
Box must go to 24" wide for all breakers
Requires an additional 6.0" box height
9
6
Box Height Addition
6
6
25