Modifications
P2 Panel Options
Enclosures
• Extra gutter to sides or ends of the can
• 24" wide boxes
• Hinged trims
*
• Door-in-door trims
*
• Screw to the box trims
*
• Trim mounted devices (Devices mounted and wired
to the trim should also have hinged trim specified)
• Pilot lights
• Toggle switches
• Push buttons
• Painted boxes
• Custom colors
• Increase gauge trims and boxes
• Stainless steel trims and boxes, Type 1
Panel Modifications
• Main Bus
Standard main bus is temperature rated tin-plated aluminum.
Bus options are 750 A/Si aluminum, tin-plated temperature
rated copper tin-plated standard – silver optional. 1000 A/Si
copper tin-plated standard – silver optional. Includes copper
neutral cross bar. For copper neutral branch lugs, see
miscellaneous.
• Split bus adds 6" to unit space
• Compression lug for MLO
• Compression lugs on main breaker (may require
extra width or length on enclosure).
• Contactor mains or submain
• Asco 920 through 225 amps. Adds 12" unit space as main,
15" unit space as submain.
• Siemens LEN through 30 amps. Adds 12" unit space.
Makes box 10" deep.
• Control power transformers (contact engineering for extra
gutter requirements)
• Branch and main breaker accessories
• Handle blocks
• Handle locks
• Aux. Contacts
• UVR
• Feed-thru lugs
• 200% neutral
• Copper lugs, mechanical
• Bus mounted TVSS
• Service entrance labeled
Accessories on 1" pole breakers (BL, BQD, ED) will take unit space.
*Contact local Siemens representative for any options & modifications.
• Grounding of panelboards
*
*
*
*
*
*
*
*
• Aluminum trims and boxes, Type 1
• NEMA 3R/12 enclosures
• NEMA 4 enclosures
• NEMA 4X enclosures
• Special keyed locks
• Gasketing trim to box
• Panel skirts
Ground bars are shipped with the panel interior factory
mounted.
• Non-insulated equipment ground bar – standard
• Copper non-insulated ground bar
• Aluminum insulated equipment ground bar
• Copper insulated equipment ground bar
• Shunt trip on main or branch
BL, BLH, HBL, ED2, ED4, HED4, HED6, HHED6 uses 1"
unit space for shunt trip. All may be used on mains
or subfeeds.
QJ2, QJ2-H, QJH2, HQJ2H, ED2, ED4, ED6, HED4, HED6,
FXD6, HFD6, JXD6, JD6, HJD6, HJXD6
• Remote control switches – mounted in a 23" enclosure
to be cable connected to the panel.
*
• Time clocks – mounted in a 23" enclosure to be cable
connected to the panel. Sangamo, tork or paragon time
*
clock can be supplied and mounted in panelboard cabinet.
*
*