Trane MCX512 G1 Installation Manual page 13

New stylus split system, 1-5 tons convertible type mcx/mwx series 60 hz
Hide thumbs Also See for MCX512 G1:
Table of Contents

Advertisement

Figure 6.
Connection
9.
Figure 7.
10. Tighten the flare nut to the specified tightening torque with torque wrench and adjustable
Table 1.
Flare Nut/Piping
Size
6.35 mm(1/4") dia.
9.53 mm(3/8") dia.
12.7 mm(1/2") dia.
15.88 mm(5/8") dia.
Figure 8.
Indoor unit
pipe
11. Repeat the process above for the remaining line.
MS-SVN15B-EN
Apply r efrigerant
lubricant her e
For proper connection, align the union tube and flare tube straight with each other, then
screw in the flare nut lightly at first to obtain a smooth match (Figure 17).
Union
Flar e nut
wrench (Figure 18).
Flare Nut Tightening Torque
Tightening
Kgf, -cm
150
350
500
600
Wrench
(adjustable)
To rque
wrench
Connection pipe
Flar e nut
Connection of Refrigerant Tubing
Torque
lbf- in
200
130
170
400
300
340
550
430
470
650
520
570
13