SMMS 4-way Air Discharge Cassette Type
To secure better effect of
heating
When it is difficult to obtain satisfactory heating
due to installation place of the indoor unit or
structure of the room, the detection temperature of
heating can be raised. Also use a circulator, etc.
to circulate heat air near the ceiling.
Follow the basic operation procedure
1
2
(
• For the CODE No. in Procedure
• For the SET DATA in Procedure
SET DATA of shift value of detection
temperature to be set up from the table below.
SET DATA
0000
0001
0002
0003
0004
0005
0006
To select horizontal wind
direction
1. Push
four seconds when the air conditioner is not
working.
Indicates CODE No. [01].
2. Select an indoor unit to be set by pushing
Indoor unit number changes each time you
push the button.
UNIT No.
The fan of the selected unit runs and the
louvers start swinging.
3. Change the CODE No. to [45] with
"TEMP."
4. Select wind direction setting with "TIME"
buttons.
Wind
direction
SET DATA
0000
0002
25-EN
3
4
5
6
).
Detection temp shift value
No shift
+1°C
+2°C (Factory setting)
+3°C
+4°C
+5°C
+6°C
and "TEMP."
buttons for at least
flashes.
button (left side of the button).
UNIT No.
1-1
1-2
No
UNIT No.
display
1-4
buttons.
Wind direction setting
Smudge reducing position
(Air direction to reduce ceiling
contamination) [Factory setting]
Cold draft position
(Air direction to control cold air fall)
5. Push
The display state changes from flashing to
lighting, and the setting is fixed.
6. Push
* When the cold draft position is selected, ceiling
contamination is less reduced.

How to set up swing type

1. Push
3
air conditioner is not working.
, specify [06].
4
, select the
Indicates CODE No. [F0].
2. Select an indoor unit to be set by pushing
Each time you push the button, unit numbers
change as follows:
The fan of the selected unit runs and the
louvers start swinging.
3. Select a swing type by pushing "TIME"
buttons.
Swing SET DATA
UNIT No.
1-3
Do not set the swing SET DATA to "0000".
(This setting may cause a failure of the louvers.)
– 25 –
Installation Manual
button to check the setting.
button to end the setting.
for at least four seconds when the
flashes.
(left side of the button).
UNIT No.
UNIT No.
1-1
1-2
No
UNIT No.
display
1-4
Swing SET DATA
Swing of louvers
Standard swing
0001
(Factory setting)
0002
Dual swing
0003
Cycle swing
CAUTION