MNMX
Minimum and Maximum Input Function Parameter Command
Input:
MNMX <input>, <source>[term]
a,n
Format:
<input>
<source>
Example: MNMX B,3[term] – Input B min/max function is on and processes data from the input sensor
units reading.
MNMX?
Minimum and Maximum Input Function Parameter Query
Input:
MNMX? <input>[term]
Format: a
<input>
Returned: <source>[term]
Format: n
MNMXRST
Minimum and Maximum Function Reset Command
Input:
MNMXRST[term]
Remarks: Resets the minimum and maximum data for all inputs.
MODE
Remote Interface Mode Command
Input:
MODE <mode>[term]
n
Format:
<mode>
Example: MODE 2[term] – Places the Model 331 into remote mode with local lockout.
MODE?
Remote Interface Mode Query
Input:
MODE?[term]
Returned: <mode>[term]
n
Format:
MOUT
Control Loop Manual Heater Power (MHP) Output Command
Input:
MOUT <loop>, <value>[term]
n,±nnnnnn[term]
Format:
<loop>
<value>
Example: MOUT 1,22.45[term] – Control Loop 1 manual heater power output is 22.45%.
MOUT?
Control Loop Manual Heater Power (MHP) Output Query
Input:
MOUT? <loop>[term]
Format: n
<loop>
Returned: <value>
Format: ±nnnnnn[term]
Remote Operation
Lake Shore Model 331 Temperature Controller User's Manual
Specifies input to configure: A or B.
Specifies input data to process through max/min. Valid entries: 1 = kelvin,
2 = Celsius, 3 = sensor units, 4 = linear data.
Specifies which input to query: A or B.
(Refer to command for description)
0 = local, 1 = remote, 2 = remote with local lockout.
(Refer to command for description)
Specifies loop to configure: 1 or 2.
Specifies value for manual output.
Specifies which loop to query: 1 or 2.
(Refer to command for description)
6-35