Installation; Location And Stacking; Input Wiring - Lincoln Electric IDEALARC R3R-300 Operator's Manual

Hide thumbs Also See for IDEALARC R3R-300:
Table of Contents

Advertisement

A-1

LOCATION AND STACKING

WARNING
FALLING EQuIPMENT can cause
injury.
• Do not lift this machine using lift
bail if it is equipped with a heavy
accessory such as trailer or gas cylinder.
• Lift only with equipment of adequate lifting
capacity.
• be sure machine is stable when lifting.
Install the welder in a dry location where there is a free
circulation of air in through the front louvers and out the
back of the case. A location which minimizes the
amount of smoke and dirt drawn into the front louvers
reduces the chance of dirt accumulation that can block
air passages, causing overheating and nuisance shut-
down of the machine.
®
The Idealarc
R3R welders can be stacked three high
when the following precautions are observed:
1. Be sure the bottom machine is on a firm, level sur-
face suitable for the total weight {up to 1350 pounds
(608 Kg)} of the stacked machines.
2. Stack the machines with the fronts flush. Be certain
the pins on the top front corners of the lower
machines fit through the holes in the base rails of
the upper machines.
3. No unit heavier than the bottom unit should be
stacked on top of it. For example, an R3R-500 shall
not be stacked on top of an R3R-400, but an R3R-
400 may be stacked on top of an R3R-500.

INPuT WIRING

WARNING
ELECTRIC ShOCK can kill.
• have an electrician install and ser-
vice this equipment.
• Turn the input power off at the fuse
box before working on equipment.
• Do not touch electrically hot parts.
RATINGS
Transformer insulation class 155°(F)
IP21 enclosure protection

INSTALLATION

Dual or triple voltage (eg: 230/460, 220/380/440, etc.)
models are shipped connected for highest voltage. To
change the connection, see the wiring or connection
diagram pasted to the inside of the access panel in the
case back.
Be sure the voltage, phase and frequency of the input
power is as specified on the welder nameplate.
Have a qualified electrician remove the access panel in
the case back and connect the three phase AC power
to terminals L
dance with the U. S. National Electrical Code, all local
codes, and the wiring diagram located inside the
machine.
The welder frame must be grounded. A stud marked
with the symbol       located on the floor of the input
box is provided for this purpose. See the U.S. National
Electrical Code for details on proper grounding
methods.
For 60 hertz, 3 phase Welders at 60% Duty Cycle.
Welder Volts
300
400
500
This welder is rated for 60% duty cycle. Duty cycle is
based on a ten minute period. Therefore, the welder
can be operated at nameplate rated output for 6 min-
utes of every 10 minute period without overheating.
An amber high temperature warning light provides a
visual indication of an over temperature condition.
Failure to follow these instructions can cause
immediate failure of components within the
machine.
When powering welder from a generator be sure to
turn off welder first, before generator is shut down,
in order to prevent damage to welder!
IDEALARC® R3R, -300, -400, -500
, L
, L
of the input contactor in accor-
1
2
3
Recommended Input Wire,
Ground Wire and Fuse Sizes
based on u.S. National Electrical Code.
Copper Wire Size
Type 75°C in Conduit
Input Amps
3 Input
1 Ground Super Lag Fuse
Input
Wires
230
56.0
8
460
28.0
10
230
82.0
6
460
41.0
10
230
100.0
4
460
50.0
8
CAuTION
A-1
Wire
Size in Amps
8
80
10
40
6
125
10
60
6
150
8
70