Operation Sequence Of The Burner - Riello RS 70/E MZ Installation, Use And Maintenance Instructions

Blown type gas burners
Table of Contents

Advertisement

Start-up, calibration and operation of the burner
5
5.7

Operation sequence of the burner

Signal ON
Signal OFF
Any signal is allowed
Number of the phase
Thermostat/pressure switch
safety TS
Thermostat/pressure switch
indicator TL
Ionisation probe ION
Air pressure switch PA
Minimum gas pressure switch
PGmin
Maximum gas pressure switch
PGM
Gas pressure switch for leak
detection PGVP
Alternative to leak detection CPI
Fan motor MV
Ignition transformer TA
Shutoff valve
Safety valve V1
Adjustment valve V2
Pilot valve VP
Limit lockout
Pos. of post-purging
Pos. without load
Pos. of post-purging
Pos. without load
D7727
List of the phases
Ph00
Lockout phase
Ph01
Safety phase
Ph10
t10 = closure in pause
Ph12
Standby
Ph22
t22 = Uphill train of the fan motor (fan motor = ON,
safety valve = ON)
Ph24
The burner moves to the pre-purging position
Ph30
t1 = pre-purging time
Ph36
The burner moves to the ignition position
Ph38
t3 = pre-ignition time
Ph40
TSA1 = safety time 1 (ignition transformer ON)
Ph42
TSA1 = safety time 1 (ignition transformer OFF), t42 =
pre-ignition time OFF
00
01
10 12 22 24 30 36 38 40 42 44 60 62 70 72 74
P
P
Pa
P
P
P
90°
Nominal load
Ignition load
Low flame
90°
Nominal load
Ignition load
Low flame
Operation
Start-up
Switching off
t1
TSA1
Ph44
t44 = interval time 1
Ph60
Operation
Ph62
t62 = max. time to reach the low flame (the burner
moves to the switch-off position)
Ph70
t13 = post-combustion time
Ph72
The burner moves to the post-purging position
Ph74
t8 = post-purging time
Ph80
t80 = emptying time (valve leak detection)
Ph81
t81 = atmospheric test time (valve leak detection)
Ph82
t82 = filling time (valve leak detection)
Ph83
t83 = pressure test time (valve leak detection)
Ph90
Standby time due to lack of gas
Ph = Phase
Checking of
seal
80 81 82 83
90
Fig. 34