J1-7)
Switch for fan speed during thermostat OFF in HEAT operation.
Provided : EXTRA LOW
Not provided : LOW
J1-8)
Switch for fan speed during thermostat OFF in HEAT operation.
Provided : EXTRA LOW or LOW (set with J1-7)
Not provided : Low or HIGH (set with remote controller)
J1-9)
Swtich for detecting abnormalities in the outdoor unit abnormality detection.
Provided : When an abnormality occurs, it is detected.
Not provided : Even if an abnormality occurs, it can not be detected.
J1-10)
Switch for auto restart function.
Provided : This function does not work.
Not provided : This function works.
(3) SW2 (Address selector)
1 2 3 4 5 6
ON
OFF
(4) SW3 (Emergency operation switch)
Normal operation
For emergency cooling
1 2
ON
ON
OFF
OFF
(5) SW5 (Model selector)···PK12FK only
1 2 3 4
ON
OFF
SW5-1) Power supply
SW5-2) OFF:For models with heat pump
ON:For models without heat pump
SW5-3) Not for use
SW5-4) This switch is unavailable for PKH-FKHA. Keep this switch at OFF.
(6) SW6 (Model selector)
1 2 3 4
ON
OFF
(7) SW7 (Model selector)
Switch to set the output of phase-controlled indoor fan motor.
Address setting is available at any time
The initial factory setting by is based on each capacity.
Models
ON
SW7
OFF
(8) J5 (Model selector)
2
4
J5-2)
Prouided
Not Previded :For models without heat pump.
J5-4)
This jumper is unavailable for PK-FK.
36
Used in setting the unit-address for group control.
For further information, refer to page 56.
For emergency heating
1 2
ON
OFF
ON :230V/240V
(
)
OFF:220V
Single control
SW6-1
OFF
SW6-2
OFF
SW6-3
OFF
SW6-4
OFF
PK12FK
PK18, 24FK
ON
OFF
1 2 3 4
1 2 3
:For models with heat pump.
1 2
Twin control
Triple control
ON(Twin NO.1) ON(Triple NO.1)
ON(Twin NO.2) ON(Triple NO.2)
OFF
ON(Triple NO.3)
OFF
ON
PK30,36FK
ON
OFF
1 2 3 4