LED indication
No.
Symptom
LED1(Red) LED2(Yellow)
Outdoor unit
operates.
20
Once
Lighting
21
Twice
Lighting
22
3 times
Lighting
23
4 times
Lighting
24
5 times
Lighting
Outdoor unit
25
9 times
Lighting
operates
26
Lighting Lighting
Abnormal point/ Con-
dition
Primary current pro-
The input current exceeds 15 A.
tection
Secondary current pro-
The current of the compressor exceeds 15 A.
tection
High-Pressure protec-
The indoor gas pipe temperature exceeds 45°C during heating.
tion
Defrosting in cooling
The indoor gas pipe temperature falls 3°C or below during
cooling.
Discharge temperature
The discharge temperature exceeds 100°C during operation.
protection
Low discharge tem-
The frequency of the compressor is kept 80 Hz or more and
perature protection
the discharge temperature is kept under 39°C for more than 20
minutes.
Cooling high-pressure
The outdoor heat exchanger temperature exceeds 58°C during
protection
operation.
Inverter check mode
The unit is operated with emergency operation switch.
Normal
www.ilmalämpöpumput.com
Condition
—
33
Correspondence
These symptoms do not mean any
abnormality of the product, but
check the following points.
• Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit aircir-
culation is short cycled.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 11-5.
"Check of LEV".
• Refer to 11-5.
"Check of outdoor
thermistors''.
• Refer to 11-5.
"Check of LEV".
• Check refrigerant circuit and refrig-
erant amount.
This symptom does not mean any
abnormality of the product, but
check the following points.
• Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air
circulation is short cycled.
—
—