LED indication
No.
Symptom
LED1(Red) LED2(Yellow)

Outdoor unit

operates.
20
Once
Lighting
21
Twice
Lighting
22
3 times
Lighting
23
4 times
Lighting
24
5 times
Lighting
Outdoor unit
25
9 times
Lighting
operates
26
Lighting Lighting
Abnormal point/ Con-
dition
Primary current pro-
The input current exceeds 15 A.
tection
Secondary current pro-
The current of the compressor exceeds 15 A.
tection
High-Pressure protec-
The indoor gas pipe temperature exceeds 45°C during heating.
tion
Defrosting in cooling
The indoor gas pipe temperature falls 3°C or below during
cooling.
Discharge temperature
The discharge temperature exceeds 100°C during operation.
protection
Low discharge tem-
The frequency of the compressor is kept 80 Hz or more and
perature protection
the discharge temperature is kept under 39°C for more than 20
minutes.
Cooling high-pressure
The outdoor heat exchanger temperature exceeds 58°C during
protection
operation.
Inverter check mode
The unit is operated with emergency operation switch.
Normal
www.ilmalämpöpumput.com
Condition
33
Correspondence
These symptoms do not mean any
abnormality of the product, but
check the following points.
• Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit aircir-
culation is short cycled.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 11-5.
"Check of LEV".
• Refer to 11-5.
"Check of outdoor
thermistors''.
• Refer to 11-5.
"Check of LEV".
• Check refrigerant circuit and refrig-
erant amount.
This symptom does not mean any
abnormality of the product, but
check the following points.
• Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air
circulation is short cycled.