OPERATING PROCEDURE
3. Removing the outdoor fan motor
(1) Remove the cabinet. (Refer to 1.)
(2) Disconnect the connector and remove the hooked lead
wire from the fan motor.
(3) Remove the propeller nut and remove the propeller.
(4) Remove screws fixing the outdoor fan motor.
(5) Remove the outdoor fan motor.
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1.)
(2) Remove the relay panel.
(3) Remove the soundproof felt.
(4) Remove the terminal cover on the compressor.
(5) Disconnect lead wires from the glass terminal of the com-
pressor.
(6) Recover gas from the refrigerant circuit.
(7) Disconnect the welded part of the discharge pipe.
(8) Disconnect the welded part of the suction pipe.
(9) Remove nuts fixing the compressor.
(10) Remove the compressor.
NOTE
Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm
Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.
2
(MPa).
Photo 4
Propeller
Photo 5
Discharge
pipe
Compressor
33
PHOTOS
Hook
Propeller nut
Soundproof felt
Compressor set nuts
Suction
pipe