ABB REF601 Product Manual page 8

Feeder protection and control
Hide thumbs Also See for REF601:
Table of Contents

Advertisement

Feeder Protection
REF601
Product version: 2.0
Table 5. Binary input
Description
Rated voltage
Operating range
Current drain
Power consumption / input
Input sensing time
Table 6. Double-pole power output relay with TCS function (Trip 2 output - Normally open, pulsed contact)
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC
(two contacts connected in series)
Minimum contact load
Trip-circuit supervision (TCS):
• Control voltage range
• Current drain through the supervision circuit
• Minimum voltage over the TCS contact
Table 7. Single-pole power output relay (Trip 1 output - Normally closed, pulsed contact)
Description
Rated voltage
Continuous contact carry
GUID-89A9F7DF-FB82-4E8D-B449-7C0BB51C1DCA V1 EN
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 35/220 V DC
Minimum contact load
Pulse duration of contact operation
8
Value
24...240 V AC / DC
85...110% of U
for AC and 70...120% of U
aux
2...20 mA
< 0.5 W
100 ms
Value
240 V AC / DC
8 A
15 A
30 A
5 A / 3 A / 1 A
100 mA at 24 V AC / DC
48...250 V AC / DC
~ 1.5 mA
20V AC / DC (15...20 V)
Value
240 V AC / DC
8A
15 A
30 A
5A / 0.2 A
100 mA at 24 V AC / DC
200 msec
1MDB07207-YN
for DC
aux
ABB