ABB REF601 Product Manual page 11

Feeder protection and control
Hide thumbs Also See for REF601:
Table of Contents

Advertisement

Feeder Protection
REF601
Product version: 2.0
Table 13. Electromagnetic compatibility tests, continued
Description
Emission tests:
• Conducted
150 kHz-0.5 MHz
0.5 MHz-30 MHz
• Radiated
30-230 MHz
230-1000 MHz
Table 14. Insulation tests
Description
Dielectric test
• Test voltage
Impulse voltage test
• Test voltage
Insulation resistance test
• Isolation resistance
Table 15. Mechanical tests
Description
Vibration tests
• Response
• Endurance / Withstand
Shock tests
• Response
• Endurance / Withstand
Bump tests
ABB
Type test value
< 66 dB ( μV/m)
< 60 dB ( μV/m)
< 40 dB ( μV/m)
< 47 dB ( μV/m)
Type test value
2 kV, 50 Hz, 1 min
5 kV, 1.2/50 μs, 0.5 J
Ω
> 100 M
at 500 V DC
Type test value
10...150 Hz, 0.035 mm / 1.0 g,
1 sweep / axis
10...150 Hz, 2.0 g,
20 sweeps / axis
10 g, 3 pulses in each direction
30 g, 3 pulses in each direction
20 g, 1000 bumps in each direction
1MDB07207-YN
Reference
IEC 60255-25
EN 55011-CISPR II
Reference
IEC 60255-5
IEC 60255-27
IEC 60255-5
IEC 60255-27
IEC 60255-5
IEC 60255-27
Reference
IEC 60255-21-1, class II
IEC 60255-21-2, class II
IEC 60255-21-2, class II
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 605 series

Table of Contents