Amana GUX-X Installation Instructions Manual page 17

Gas-fired warm-air furnace
Hide thumbs Also See for GUX-X:
Table of Contents

Advertisement

TANKS AND PIPING - PROPANE GAS UNITS
WARNING
To prevent death, personal injury or
property damage due to fire or explosion
caused by a propane gas leak, install a gas
detecting warning device. Since rust can
reduce the level of odorant in propane gas,
a gas detecting warning device is the only
reliable way to detect a propane gas leak.
Contact a local propane gas supplier about
installing a gas detecting warning device.
All propane gas equipment must conform to the safety
standards of the National Board of Fire Underwriters (See
NBFU Manual 58).
For satisfactory operation, propane gas pressure must be
10 inch W.C. at the furnace manifold with all gas appli-
ances in operation. Maintaining proper gas pressure de-
pends on three main factors:
1. Vaporization rate, depending on temperature of the
liquid, and "wetted surface" area of the container or
containers.
2. Proper pressure regulation. Two-stage regulation is
recommended for both cost and efficiency.
3. Pressure drop in lines between regulators, and be-
tween second stage regulator and the appliance. Pipe
size will depend on length of pipe run and total load of
all appliances.
Complete information regarding tank sizing for vaporiza-
tion, recommended regulator settings, and pipe sizing is
available from most regulator manufacturers and propane
gas suppliers.
Since propane gas will quickly dissolve white lead or most
standard commercial compounds, special pipe dope must
be used. Shellac base compounds resistant to the actions
of liquefied petroleum gases such as Gasolac, Stalactic,
Clyde's or John Crane are satisfactory.
Refer to Figure 19 for typical propane gas installations.
Figure 19
Propane Gas Installations (Typ.)
PROPANE GAS PIPING CHARTS
Sizing Between First and Second Stage Regulator
Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting.
Capacities in 1,000 BTU/hour.
Pipe or
Tubing
Tubing Size, O.D. Type L
Length,
3/8"
1/2"
Feet
10
730
1,700
20
500
1,100
30
400
920
40
370
850
50
330
770
60
300
700
80
260
610
100
220
540
125
200
490
150
190
430
175
170
400
200
160
380
To convert to capacities at 15 psig settings - multiply by 1.130
To convert to capacities at 5 psig settings - multiply by 0.879
Sizing Between Single or Second Stage Regulator and Appliance*
Maximum Propane Capacities Listed are Based on 1/2" W.C. pressure drop at 11" W.C. setting.
Capacities in 1,000 BTU/hour.
Pipe or
Tubing
Tubing Size, O.D. Type L
Length,
3/8"
1/2"
5/8"
Feet
10
39
92
199
20
26
62
131
30
21
50
107
40
19
41
90
50
18
37
79
60
16
35
72
80
13
29
62
100
11
26
55
125
10
24
48
150
9
21
43
200
8
19
39
250
8
17
36
*Data in accordance with NFPA pamphlet NO. 54
WARNING
To prevent death, serious personal injury
or property damage due to fire or explosion
caused by a propane gas leak, install a gas
detecting warning device.
If the propane gas furnace is installed in a
basement, an excavated area or a confined
space, a warning device is required due to:
• Propane gas is heavier than air and any
leaking gas can settle in any low areas
or confined spaces.
• Propane gas odorant may fade, making
the gas undetectable except with a
warning device.
If the presence of gas is suspected, follow
the instructions on Page 2 of this manual.
17
Nominal Pipe Size
Schedule 40
5/8"
3/4"
7/8"
1/2"
3,200
5,300
8,300
3,200
2,200
3,700
5,800
2,200
2,000
2,900
4,700
1,800
1,700
2,700
4,100
1,600
1,500
2,400
3,700
1,500
1,300
2,200
3,300
1,300
1,200
1,900
2,900
1,200
1,000
1,700
2,600
1,000
900
1,400
2,300
900
830
1,300
2,100
830
780
1,200
1,900
770
730
1,100
1,800
720
Nominal Pipe Size
Schedule 40
3/4"
7/8"
1-1/8"
1/2"
3/4"
1"
329
501
935
275
567
1,071 2,205 3,307
216
346
630
189
393
732
181
277
500
152
315
590
145
233
427
129
267
504
131
198
376
114
237
448
121
187
340
103
217
409
104
155
289
89
185
346
90
138
255
78
162
307
81
122
224
69
146
275
72
109
202
63
132
252
66
100
187
54
112
209
60
93
172
48
100
185
3/4"
7,500
4,200
4,000
3,700
3,400
3,100
2,600
2,300
2,100
1,900
1,700
1,500
1-1/4" 1-1/2"
1,496 2,299
1,212 1,858
1,039 1,559
913
1,417
834
1,275
724
1,066
630
976
567
866
511
787
439
665
390
590