Fan And Fan Motor - Mitsubishi Electric City Multi PLFY-P06NLMU-E Technical & Service Manual

Ceiling cassettes plfy series
Hide thumbs Also See for City Multi PLFY-P06NLMU-E:
Table of Contents

Advertisement

8-3.Fan and fan motor

OPERATING PROCEDURE
1. Remove the service panel and filter with the pro-
cedure explained in section 8-1.
2. Remove the two screws fixing the bell-mouth (A),
and remove the bell-mouth A. (Fig. 3-1)
3. Remove the turbo fan mounting screw (one M8
nut), and pull the turbo fan off the fan motor shaft.
(Photograph 3-1)
Note: The turbo fan will come off the motor shaft
when the mounting screw is removed, so take
care not to let turbo fan fall off when removing
it.
4. Remove the lead wire retainer. (Two screws)
(Photograph 3-3)
5. Disconnect the motor lead wire connector in the
control box.
• Motor on the control box side
Remove the connector cover, and remove the
motor lead wire connector.
• Motor on the opposite control box side
(Photograph 3-1)
(1) Remove the protection cover on the control box
side.
(2) Remove the lead wire, pick the tab of the con-
nector, and push it into the motor side.
6. Remove the mounting nuts (four M5 nuts) fixing
the motor fixing leg and main body, and remove
the fan motor together with the leg.
(Photograph 3-3)
Note: The fan motor will come off the main body when
the mounting screw is removed. It could fall off,
so when removing, securely hold the fan motor
and remove the mounting screws.
19
Be careful removing heavy parts.
PHOTOS&ILLUSTRATIONS
(Fig.3-1)
(Photo.3-1)
(Photo.3-2)
Push into the opposite
control box side.
Tab
Lead wire
Protection
cover
(Photo.3-3)
Lead wire retainer
(A) Bell-mouth
Hooks
Mounting nut
Tab
Control box side
Mounting nut