3-2. Electrical parts specifications
Model
Symbol
Parts
name
Tranrsformer
T
Liquid pipe
TH22
thermistor
Gas pipe
TH23
thermistor
Outdoor air
temperature
TH24
thermistor
Fuse
FUSE
(Indoor con-
troller board)
Fan motor
(with Inner-
MF1,2
thermostat)
Inner-
thermostat
(Fan motor)
Fan motor
C1
capacitor
Linear
LEV
expansion valve
Power supply
TB2
terminal block
Transmission
TB5
terminal block
TB15
7
PEFY-P30NMHU-E-F
(Primary) 50/60Hz 220-240V (Secondry) (23.5V 0.9A)
Resistance 0˚C[32˚F]/15kΩ,10˚C[50˚F]/9.6kΩ,20˚C[68˚F]/6.3kΩ,25˚C[77˚F]/5.4kΩ,
Resistance 0˚C[32˚F]/15kΩ,10˚C[50˚F]/9.6kΩ,20˚C[68˚F]/6.3kΩ,25˚C[77˚F]/5.4kΩ,
Resistance 0˚C[32˚F]/15kΩ,10˚C[50˚F]/9.6kΩ,20˚C[68˚F]/6.3kΩ,25˚C[77˚F]/5.4kΩ,
4-pole OUTPUT 90W
NS-80VMHF
4.0µF✕440V
DC12V Stepping motor drive
port dimension ø 5.2
0~1800pulse
<at R410A outdoor unit>
0~2000pulse
<at the other outdoor unit>
(L1,L2,G) 330V 30A
PEFY-P54NMHU-E-F
30˚C[86˚F]/4.3kΩ,40˚C[104˚F]/3.0kΩ
30˚C[86˚F]/4.3kΩ,40˚C[104˚F]/3.0kΩ
30˚C[86˚F]/4.3kΩ,40˚C[104˚F]/3.0kΩ
250V 6.3A
4-pole OUTPUT 130W
NS-100VMHF
OFF 135˚C±5˚C[275˚F±41˚F]
ON 95˚C±20˚C[203˚F±59˚F]
DC12V Stepping motor drive
port dimension ø 6.4
0~1800pulse
<at R410A outdoor unit>
0~2000pulse
<at the other outdoor unit>
(1,2),(M1,M2,S) 300V 10A
PEFY-P72NMHU-E-F
4-pole OUTPUT 200W
NS-224M-C-F
-
DC12V Stepping motor drive
port dimension ø 5.2
0~1800pulse
<at R410A outdoor unit>
0~2000pulse
<at the other outdoor unit>
(L1,L2,L3,G) 660V 40A
PEFY-P96NMHU-E-F
4-pole OUTPUT 230W
NS-280M-C-F