WDV Series Gas Fireplace
Foundation
Recess
Watertight Seal
Around Pipe
Figure 17 -
Snorkel Installation, Recessed Foundation
FP1966
•
Do not back fill around snorkel.
snorkel
•
a clearance of at least 4" must be
maintained between the snorkel and
the soil.
VertIcal (thrOuGh-the-rOOF)
applIcatIOns
This gas fireplace has been approved for,
•
Vertical installations up to 40' (1 m) in height. Up to
a 10' (3 m) horizontal vent run can be installed within
the vent system using a maximum of two 90° elbows.
Figure 18
nOte: Horizontal and vertical sections of this vent system
require a minimum 1" clearance to combustibles at the top,
sides and bottom.
40' Maximum Height
1' Minimum Height
1" Min.
FP1183
Figure 18 -
Support Straps for Horizontal Runs
16
FP1183
Snorkel
Wall Screws
Sheet Metal
Screws
10'
Maximum
Support Straps
Every 3'
•
Up to two 45° elbows may be used within the horizontal
run. For each 45° elbow used on the horizontal plane,
the maximum horizontal length must be reduced by 18"
(450 mm).
Example: Maximum horizontal length
No elbows = 10' (3 m)
1x45° elbows = 8.5' (.6 m)
x45° elbows = 7' (.1 m)
•
A minimum of an 1' (3.6 m) vertical rise is
required.
•
Two sets of 45° elbows offsets may be used within
the vertical sections. From 0 to a maximum of 8'
(.5 m) of vent pipe can be used between elbows.
Figure 19
•
The maximum angular variation allowed in the
system is 70°. Figure 19
Example:
Total Angular Variation =
1
2
3
4
1" Min.
Figure 19 -
Maximum Elbow Usage
VentInG InstallatIOn
Elbow 1 =
Elbow =
Elbow 3 =
Elbow 4 =
FP1179
78D0011
90°
45°
45°
90°
70°
1
2
3
4