Powerware 5125 Tower User Manual page 26

1000va, 1500va, 2000va, 2200va
Table of Contents

Advertisement

Table 7. Battery
Configuration
EBM Configuration
Type
Charging
Monitoring
Table 8. Battery Run Times (in Minutes at Full/Half Load)
Model
Internal UPS Batteries
1000VA;
1500VA;
2000VA;
2200VA;
NOTE Battery times are approximate and vary depending on the load configuration and battery charge
Powerware reserves the right to change specifications without prior notice.
1000VA; (2) 24V, 9 Ah internal batteries
1500VA; (4) 48V, 7.2 Ah internal batteries
2000VA; (4) 48V, 12 Ah internal batteries
2200VA; (4) 48V, 12 Ah internal batteries
EBM-24; (8) 24V, 9 Ah batteries
EBM-48; (8) 48V, 9 Ah batteries
Sealed, maintenance free, valve regulated, lead-acid
Internal battery; less than 3 hours to 90% usable capacity at nominal after
full load discharge
External battery; recharging at 80% load or less is recommended, no more
than 16x discharge time to 90% usable capacity at nominal line voltage after
full load discharge; an external battery charger is recommended for faster
recharge times when using more than 2 EBMs
Advanced monitoring for earlier failure detection and warning, auto detection
of additional EBMs
1 EBM
5/14
25/60
6/17
33/79
5/16
29/67
5/14
26/60
2 EBM
3 EBM
55/170
83/199
63/146
92/174
62/190
91/222
55/170
81/198
23
4 EBM
109/228
120/201
119/251
106/224