Kenmore TSTAT0713K Owner's Manual page 21

1 for all programmable temperature & humidity
Hide thumbs Also See for TSTAT0713K:
Table of Contents

Advertisement

Advanced Setup
DEHUMIDIFICATION TERMINAL - The DEHUM terminal may
be programmed to operate in one of two ways:
1) Normally Closed (NC): The thermostat will de-energize the
DEHUM terminal to allow the fan to run in low speed when
there is a call for 1st stage cooling and the room humidity is
greater than the dehumidification setpoint.
2) Normally Open (NO): The thermostat will energize the
DEHUM terminal to allow the fan to run in low speed when
there is a call for 1st stage cooling only and the room humidity
is greater than the dehumidification setpoint.
NC
Normally Closed (NC) =
DEHUM deenergized for
low speed fan.
Normally Open (NO) =
DEHUM energized for
low speed fan.
NO
2I
o
Setup
Dehumidify
Page 20
Press
PROGRAM
To Exit

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents