Potterton Gold HE A Range Installation & Service Instructions Manual page 16

Gold he a range condensing combination boiler
Hide thumbs Also See for Gold HE A Range:
Table of Contents

Advertisement

Gas Service Cock
Fig. 10
Zone 1
Zone 0
Window
Recess
Fig. A
Zone 1
Zone 0
Fig. B
16
© Baxi Heating UK Ltd 2012
Zone 2
Window
Recess
Zone 2
0.6 m
Zone 2
In GB Only
Window Recess
Zone 2
Outside Zones
2.25 m
Zone 2
0.6 m
In GB Only
1. Where the appliance is installed in a cupboard or
compartment, no air vents are required.
2. BS 5440: Part 2 refers to room sealed appliances installed
in compartments. The appliance will run sufficiently cool
without ventilation.
1. The gas installation should be in accordance with the
relevant standards. In GB this is BS 6891. In IE this is the
current edition of I.S. 813 "Domestic Gas Installations".
2. The connection to the appliance is a 22mm copper tail
located at the rear of the gas service cock (Fig. 10).
3. Ensure that the pipework from the meter to the
appliance is of adequate size. Do not use pipes of a smaller
diameter than the boiler gas connection (22mm).
1. External wiring must be correctly earthed, polarised and
in accordance with relevant regulations/rules. In GB this is
the current I.E.E. Wiring Regulations. In IE reference should
be made to the current edition of ETCI rules.
2. The mains supply is 230V ~ 50H z fused at 3A.
Ceiling
1. If the boiler is installed in a room containing a bath or
shower it CANNOT be fitted in Zone 1 or Zone 2 (Figs. A
& B shows Z one dimensions for a bathtub. For other
examples refer to the Current I.E.E. Wiring Regulations) and
reference must be made to the relevant requirements.
In GB this is the current I.E.E. Wiring Regulations and
Building Regulations.
In IE reference should be made to the current edition of I.S.
813 "Domestic Gas Installations" and the current ETCI rules.
2. If the integral timer is replaced with the blanking plate
supplied in the installation kit it can be fitted in Zone 2.
7.0 Site Requirement
7.3
Ventilation of Compartments
7.4
Gas Supply
7.5
Electrical Supply
NOTE: The method of connection to the electricity
supply must facilitate complete electrical isolation of the
appliance.
Connection may be via a fused double-pole isolator with
a contact separation of at least 3mm in all poles and
servicing the boiler and system controls only.
7.6
Bath & Shower Rooms