Vertical Term's With (Or Without) 2 45° Elbows - Travis Industries Avalon Owner's Manual

Direct vent freestanding stove
Hide thumbs Also See for Avalon:
Table of Contents

Advertisement

10
Vertical Terminations with 0, 2, or 4 45° Offsets
Offset Length
None
1' Section
2' Section
3' Section
4' Section
The termination must fall within the shaded area shown in the
chart. Use the indicated restrictor position.
Zero or Two 45° Offsets
38' (max)
35 feet
30 feet
NOTE:
Restrictor positions are based upon lab tests. The
ideal restrictor position may vary slightly, especially
25 feet
when the termination is near the demarkation line.
20 feet
15 feet
10 feet
(min.)
5 feet
0 feet
Travis Industries
Installation
Hor. Offset
Vert. Rise
5"
1'
1' 9"
2' 5"
3' 2"
Restrictor
Position # 7
Restrictor
Position # 1
NOTE:
The maximum offset lengths,
combined, is four 4' sections.
(for qualified installers only)
1'
1' 7"
2' 4"
3'
3' 8"
38' (max)
38' (max)
35 feet
35 feet
30 feet
30 feet
25 feet
25 feet
20 feet
20 feet
15 feet
15 feet
10 feet
10 feet
(min.)
(min.)
5 feet
5 feet
0 feet
0 feet
9 3 5 0 8 1 2 2
Horizontal
Offset
Vertical
Rise
Offset
Length
Four 45° Offsets
Restrictor
Position # 7
NOTE:
Restrictor positions are based upon
lab tests. The ideal restrictor position
may vary slightly, especially when the
termination is near the demarkation
line.
Restrictor
Position # 1
NOTE:
The maximum offset
lengths, combined, is
four 4' sections.
38' (max)
35 feet
30 feet
25 feet
20 feet
15 feet
10 feet
(min.)
5 feet
0 feet
1 4 1 1 0 0