Installation
10
Approved Venting Configurations for Vertical Terminations with
Zero, Two, or Four 45° Elbows
10' Minimum System
Height
(with or without offsets)
40' Maximum System
Height
24' Maximum Offset
The termination must fall
within the shaded area
shown in the chart. Use
the indicated restrictor
position.
If using offsets, use the
table below to calculate the
vertical rise and horizontal
offset
Horizontal
Offset
Vertical
Rise
Offset
Length
Offset Length
Hor. Offset
None
5"
1' Section
1'
2' Section
1' 9"
3' Section
2' 5"
4' Section
3' 2"
4' + 1' Section 3' 9"
4' + 2' Section 4' 6"
4' + 3' Section 5' 2"
4' + 4' Section 6'
Travis Industries
40' (max)
35 feet
30 feet
25 feet
20 feet
15 feet
10 feet
5 feet
Vert. Rise
1'
1' 7"
0 feet
2' 4"
3'
3' 8"
4' 4"
5'
5' 9"
6' 9"
(for qualified installers only)
Restrictor
Position # 6
Restrictor
Position # 5
4041220
NOTE:
Restrictor positions are based
upon lab tests. The ideal
restrictor position may vary
slightly, especially when the
termination is near a
demarkation line.
9 3 5 0 8 1 2 3
40' (max)
35 feet
30 feet
25 feet
20 feet
15 feet
10 feet
5 feet
0 feet