Carrier 42NQV025H Service Manual page 24

Table of Contents

Advertisement

7-2. Operation Data
<Cooling>
Tempeature
Model name
condition(°C)
Indoor
Outdoor
27/19
35/-
42NQV025H
42NQV035M
42NQV035H
42NQV045M
42NQV045H
<Heating>
Tempeature
Model name
condition(°C)
RAS-
Indoor
Outdoor
20/-
7/6
42NQV025H
42NQV035M
42NQV035H
42NQV045M
42NQV045H
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
Standard
Heat exchanger
pressure
pipe temp.
P (MPa)
T1 (°C)
0.9 to 1.1
12 to 14
0.8 to 1.0
11 to 13
0.8 to 1.0
11 to 13
0.7 to 0.9
10 to 12
0.8 to 1.0
11 to 13
Heat exchanger
Standard
pipe temp.
pressure
P (MPa)
T1 (°C)
2.5 to 2.7
39 to 41
2.7 to 2.9
43 to 45
2.6 to 2.8
41 to 43
2.5 to 2.7
39 to 41
2.7 to 2.9
43 to 45
24
Indoor
fan mode
T2 (°C)
37 to 39
High
39 to 41
High
46 to 48
High
47 to 49
High
40 to 42
High
Indoor
fan mode
T2 (°C)
0 to 3
High
0 to 2
High
0 to 2
High
0 to 2
High
0 to 2
High
FILE NO. SVM-07013
Outdoor
Compressor
fan mode
revolution
(rps)
High
49
High
77
High
63
High
89
High
83
Outdoor
Compressor
fan mode
revolution
(rps)
High
60
High
80
High
66
High
89
High
83