Example Of Tubing Size Selection And Refrigerant Charge Amount - Sanyo R410A Installation Instructions Manual

W-3way eco-i system air conditioner
Hide thumbs Also See for R410A:
Table of Contents

Advertisement

1-15. Example of Tubing Size Selection and Refrigerant Charge Amount

Additional refrigerant charging
Based on the values in Tables 1-3, 4, 5, 9 and 10-2 use the liquid tubing size and length, and calculate the amount of additional
refrigerant charge using the formula below.
Required additional
refrigerant charge (oz)
(a) : Liquid tubing
Total length of ø7/8" (ft.)
(b) : Liquid tubing
Total length of ø3/4" (ft.)
(c) : Liquid tubing
Total length of ø5/8" (ft.)
● Charging procedure
Be sure to charge with R410A refrigerant in liquid form.
1. After performing a vacuum, charge with refrigerant from the liquid tubing side. At this time, all valves must be in the "fully
closed" position.
2. If it was not possible to charge the designated amount, operate the system in Cooling mode while charging with refrigerant
from the gas tubing side. (This is performed at the time of the test run. For this, all valves must be in the "fully open" position.
However if only one outdoor unit is installed, a balance tube is not used. Therefore, leave the valves fully closed.)
Charge with R410A refrigerant in liquid form.
With R410A refrigerant, charge while adjusting the amount being fed a little at a time in order to prevent liquid refrigerant from
backing up.
● After charging is completed, turn all valves to the "fully open" position.
● Replace the tubing covers as they were before.
1. R410A additional charging absolutely must
CAUTION
2. The R410A refrigerant cylinder has a gray
3. The R410A refrigerant cylinder includes a
4. Due to differences in the refrigerant, pres-
Example:
Outdoor unit
09663
09663
model
model
B
● Example of each tubing length
Main tubing
LA = 131 ft.
LB = 16 ft.
LC = 16 ft.
3.93 × (a) + 2.78 × (b) + 1.99 × (c) + 1.38 × (d) + 0.602 × (e) + 0.279 × (f) + Necessary amount of
=
additional refrigerant charge per outdoor unit
be done through liquid charging.
base color, and the top part is pink.
siphon tube. Check that the siphon tube is
present. (This is indicated on the label at
the top of the cylinder.)
sure, and refrigerant oil involved in instal-
lation, it is not possible in some cases to
use the same tools for R22 and for R410A.
A
LC
LB
LA
1
2
48 model
48 model
Distribution joint tubing
Outdoor side
A = 7 ft.
B = 7 ft.
(d) : Liquid tubing
Total length of ø1/2" (ft.)
(e) : Liquid tubing
Total length of ø3/8" (ft.)
( f ) : Liquid tubing
Total length of ø1/4" (ft.)
Balance tube
Use a flathead screwdriver
and open by turning the part
with the screw groove to the
right, from "
Liquid tube
Use a hex wrench (width 5/32 inch)
and turn to the left to open.
Discharge tube
Use a flathead screwdriver
and open by turning the part
with the screw groove to the
right, from "
3
4
48 model
36 model
Indoor side
1 = 98 ft.
2 = 16 ft.
3 = 16 ft.
4 = 65 ft.
18
" to " "
Use a flathead screwdriver
and open by turning the part
with the screw groove to the
" to " "
right, from "
Suction tube
" to " "