Vermont Castings Concord 1660 Installation And Operating Manual page 10

The concord woodburning stove
Table of Contents

Advertisement

Vermont Castings Concord
wall Shields
Wall shields should be constructed of 24 gauge or
heavier sheet metal, or another noncombustible mate-
rial such as 1/2" (13 mm) insulation board (Fig. 14) or
common brick "laid on flat," with the 3¹⁄₂" (89 mm) side
down.
Shields must be spaced out from the combustible
surface 1" (25 mm) on noncombustible spacers. The
spacers should not be directly behind the stove or
chimney connector.
Air must be able to flow between the wall and the
shield. At least 50% of the bottom 1" (25 mm) of the
shield should be open and the shield must be open at
the top.
Air flow
Stud wall
framing
Wall shield
Noncombustible
spacers and
fasteners
Drywall
Air flow
fig. 14 Approved Wall shield construction
The following examples of wall shield construction illus-
ST248a
trate common designs used to safely achieve reduced
wall shield construction
clearances to combustible wall materials.
12/14/99 djt
parallel installation, vertical chimney connector,
two wall shields. Fig. 15: Reduced clearances for
both rear and side walls. Wall shields may meet at
corner if desired. Shielding for connector is centered
behind connector.
parallel installation with rear wall pass-through, two
wall shields. Fig. 16: Reduced clearances for both
rear and side walls. Wall shields may meet at corner if
desired. Shielding for connector is centered behind con-
nector. Wall pass-through must comply with codes.
corner installation, vertical chimney connector, two
wall shields. Fig. 17: Reduced side clearances. Wall
shields MUST meet at corner.
parallel installation with rear exit, rear wall pass-
through, rear wall shield. Fig. 18: Reduced clear-
ances for rear wall. Shielding for connector is centered
behind connector. Wall pass-through must comply with
codes.
10
Shield
Metal Spacer
ST248a
C
A
A
B
C
fig. 15 Parallel installation, vertical chimney connector, two
wall shields.
ST550
Madison
wall shield
11/00
A
A
B
C
fig. 16 Parallel installation with rear wall pass-through, two
wall shields.
ST551
Madison
Wall shield
BB
11/00
C
C
A
B
A
C
fig. 17 Corner installation, vertical chimney connector, two
wall shields.
ST552
Madison
Wall shield
cc
11/00
A
B
C
fig. 18 Parallel installation, rear wall pass through, rear wall
shield.
ST564Madison
wall shield
11/00
A = 48" (1219 mm)
C
B = Max. - C
C = 1" (25 mm)
B
C
ST550
A = 48" (1219 mm)
B = 48" (1219 mm)
C = 1" (25 mm)
B
C
ST551
A = 48" (1219 mm)
B = Max. - C
C = 1" (25 mm)
B
C
ST552
A = 48" (1219 mm)
B = 48" (1219 mm)
C = 1" (25 mm)
ST564
30005102