Parameter description
Display
Designation
06:09
Frost protection
06:10
Summer switch-off
06:11
Extended pump
running time
06:13
Room factor
06:14
Room thermostat
function
06:15
Room frost
protection limit
Description
Setting range:
OFF (----)
-50 °C ... +10 °C
Factory setting: 3 °C
Function:
To keep the heating system from freezing in switch-off mode, the
controller is equipped with electronic frost protection.
Caution: Faulty operation can result in damages to
building!
Setting range:
OFF (----)
10 °C ... 30 °C
Factory setting: 20 °C
Function:
Switches off the heating operation when outside temperatures
exceed the desired outside temperature.
Setting range:
0,0...60,0 Min
Factory setting: 5 min
Function:
This function determines extended run time of heating circuit
pump after heating circuit is switched off by time programs.
Setting range:
0...500%
Factory setting: 100%
Function:
This function determines to what extent a deviation of the room
temperature from the setpoint affects the control of boiler flow
temperature.
Corrected room setpoint = set room setpoint - (deviation x room
factor) / 100
Setting range:
Off (----)
0.5...5K
Factory setting: Off (---)
Function:
This function determines a room temperature limit; if limit is
exceeded, heating is turned off.
Setting range:
5...30 °C
Factory setting: 10 °C
Function:
This function determines the room temperature during switch-off
mode with activated frost-protection.
X3
X3
X3
X3, X4
X3, X4
X3, X4