Elektronikbau- und Vertriebs CETA 106 Operating Manual page 12

Heating circuit controller with differential temperature
Table of Contents

Advertisement

BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 10 Freitag, 11. Dezember 2009 1:16 13
Parameter description
Display
Designation
03:04
Building type
03:05
Climate zone
03:06
Automatic exit time
03:07
Anti-blocking
protection
03:09
Code heating
specialist
03:10
Total reset
06 Parameter heating circuit
Display
Designation
06:01
Function
10
Description
Setting range:
1: Light construction (mean value over 6 X3
hours)
2: Medium construction
(mean value over 24 hours)
3: Heavy construction
(mean value over 72 hours)
Factory setting: 2
Function:
This parameter considers the building type by adapting the
calculation of the outside temperature mean value according to
its setting.
Setting range:
-50°C ... 0°C
Factory setting: -12?
Function:
The climate zone is the coldest outside temperature value to be
expected.
Setting range:
0,5 ... 10 Min
Factory setting: 2 min
Function:
When unit is not operated during the set time, the display
returns to basic display.
Setting range:
0 = OFF
1 = ON
Factory setting: OFF
Function:
With this function activated, pump is switched on daily for ca. 20
seconds as protection against blocking during extended switch-
off phases (> 24h).
Setting range:
0 ... 999
Factory setting: 0
Function when setting is greater than 0:
Hide parameters marked with X3.
Reset to factory settings
Description
Setting range:
0=OFF
1=Unmixed circuit
2=Mixed circuit
Factory setting: 2
X3
X3
X3