Elektronikbau- und Vertriebs CETA 106 Operating Manual page 14

Heating circuit controller with differential temperature
Table of Contents

Advertisement

BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 12 Freitag, 11. Dezember 2009 1:16 13
Parameter description
Display
Designation
06:07
Heating curve/
conductance
06:08
Heating system
(Exponent)
12
Description
Setting range:
0,05 ... 3,50
Factory setting: 1,00
Function:
Determines the heating curve for the heating circuit.
Setting range:
1.00...10.00
Factory setting: 1,10
Function:
Curvature of heating circuit's heating curve.
Recommendation:1.10: Underfloor heating or
other panel heating systems
1.30:
Radiator heating
2.00:
Convector and baseboard heating
>3,00: General ventilator applications with
high start temperatures