Programming the PC5100
S
3.1 How to Program
You can program the PC5100 by entering installer's programming
Q
mode ([
] [8] [Installer's code]) at any system keypad.
All PC5100 programming is in programming section [805] (see page 8).
Ensure that you have double checked each entry for all device
serial number sections. If you have entered data which was not
accepted, the section will not change from the previous
settings and device serial numbers will revert to [00000].
3.2 Enrolling Devices
To enroll AML devices:
1. At a system keypad, enter [Q][8][Installer's code] to go to the
installer's programming section.
2. Enter programming section [805].
3. Enter the 2-digit number corresponding to the zone the device is to
occupy ([01] to [32]).
NOTE: You cannot enroll more than one device to a zone.
If you install AML devices on zones programmed as interior
and delay zone types, the delay zones must have a lower zone
number than the interior zones. For example, if zone number
[04] is a delay zone, interior zones that use AML devices can
only be installed on zones [05] or higher. If you program an
AML delay zone with a higher number than AML interior zones,
the system may detect a violation on the interior zone before
the delay zone is triggered, causing a false alarm.
4. Enter the device's serial number. The entry must be five digits.
5. The device is now enrolled on the system. Record the serial number
and the assigned zone number in the programming worksheets in
the back of this manual.
6. Continue with steps 3 - 5 until you have enrolled all devices.
7. To exit press [#].
Once you have enrolled all the AML devices, you should
program the Panel Key. See section 3.7 for more information.
3.3 Zone Programming
The AML devices will not work properly until you complete the zone and
partition programming. Select a zone definition for each used zone in
programming sections [001] – [004].
You must also enable the wireless/AML zone attribute for each zone
that has been assigned to an AML device. To do this, turn ON option 8
in the appropriate programming section (one or more of sections [101]
– [132]). See your PC5010 or PC5015 Installation Manual for more
information.
To ensure proper operation, use zone definitions (87) and (88) for both
delayed and standard fire zones on the addressable loop.
E
C
T
I
5
O
N
3