Toshiba Carrier MMU-AP0182H2UL Service Manual page 65

Split type
Hide thumbs Also See for Carrier MMU-AP0182H2UL:
Table of Contents

Advertisement

Address setup (Manual setting from Wired remote controller)
In case that addresses of the indoor units will be
determined prior to piping work after wiring work
• Set an indoor unit per a remote controller.
• Turn on power supply.
1
CL
Push
SET
+
+
TEST
for 4 seconds or more.
2
(Line address)
Using the temperature setup
buttons, set
to the CODE No.
12
3
Using timer time
set the line address.
4
Push
button. (OK when display goes on.)
SET
5
(Indoor unit address)
Using the temperature setup
buttons, set
to the CODE No.
13
6
Using timer time
set 1 to the line address.
7
Push
button. (OK when display goes on.)
SET
8
(Group address)
Using the temperature setup
buttons, set
to the CODE No.
14
9
Using timer time
set
to Individual,
0000
Header unit and
0002
10
Push
SET
button.
(OK when display goes on.)
11
Push
button.
TEST
Setup completes.
(The status returns to the usual stop status.)
Note 1)
When setting the line address from the remote controller, do not use Address 29 and 30.
As they are addresses which cannot be set to the outdoor unit, if they are set, the check code [E04] (Indoor/Outdoor
communication circuit error) is issued.
Note 2)
When an address was manually set from the remote controller and the central control over the refrigerant lines is
carried out, perform the following setting for the Header unit of each line.
• Set the line address for every line using SW13 and 14 on the interface P.C. board of the Header unit in each line.
• Except the least line address No., turn off SW30-2 on the interface P.C. board of the Header units in the lines
connected to the identical central control.
(Draw the terminal resistances of indoor/outdoor and central control line wirings together.)
• For each refrigerant line, connect the relay connector between Header unit [U1U2] and [U3U4] terminals.
• After then set the central control address.
(For setting of the central control address, refer to the Installation manual for the central control equipment.)
buttons simultaneously
/
/
buttons,
/
/
buttons,
/
/
buttons,
to
0001
to follower unit.
65