Toshiba Carrier MMU-AP0182H2UL Service Manual page 150

Split type
Hide thumbs Also See for Carrier MMU-AP0182H2UL:
Table of Contents

Advertisement

Table 2
CODE No. table (Please record the objective unit data at field)
DN
Item
01
Filter sign lighting time
02
Dirty state of filter
03
Central control address
06
Heating suction temp shift
0C
PRE-DEF indication selection
0F
Cooling only
10
Type
11
Indoor unit capacity (See below table)
12
Refrigerant line address
13
Indoor unit address
14
Group address
28
Automatic restart from power cut
2A
Option input selection (CN80)
2b
Thermo output selection (T10
2E
Input selection (T10
32
Sensor selection
60
Timer set (Wired remote controller)
69
Louver selection of cooling
Indoor unit capacity (CODE No. [11])
Setup data
0001∗
0001
MMK-AP0073H2UL
0003
MMK-AP0093H2UL
0005
MMK-AP0123H2UL
0007
MMK-AP0153H2UL
0009
MMK-AP0183H2UL
0011
MMK-AP0243H2UL
∗ Initial value of EEPROM installed on the supplied service P.C. board
Be sure to set as 0008
)
)
Model
Invalid
Memo
0001: 150 hour
0000: Standard
0099: Unfixed
0002: + 3.6°F (+2°C)
0000: Standard
0000: Heat pump
0008: High wall type
According to capacity type
0099: Unfixed
0099: Unfixed
0099: Unfixed
0000: None
0002: External emergency input
0000: Thermo ON
0000: Operation input
0000: Available
0000: Available
0000: Standard
150
At shipment