Refrigerant Piping - Toshiba MMD-AP0074BH2UL Installation Manual

Air conditioner multi type
Hide thumbs Also See for MMD-AP0074BH2UL:
Table of Contents

Advertisement

 Condensate drain pipe insulation
The condensate drain system piping must be insulated to prevent sweating after the leak check is performed. All
material used in the condensate drain system must comply with applicable codes and regulations covering
materials installed in the ceiling plenum area.
To cover the pipe and the indoor unit with a heat
insulator, do not make a space between them.
1" drain pipe
(locally procured)
Pipe insulator
(locally procured)
Fix the insulator with adhesive tape
17-EN
– 9 –
Pipe insulator
(indoor unit side)
6

Refrigerant piping

CAUTION
When the refrigerant pipe is long, provide support
brackets at intervals of 8'2" to 9'10" (2.5 to 3 m) to clamp
the refrigerant pipe. Otherwise, abnormal sound may be
generated.
Use the flare nut attached with the indoor unit or R410A
flare nut.
 Permissible piping length and
height difference
They vary depending on the outdoor unit. For details,
refer to the Installation Manual attached to the outdoor
unit.
 Pipe size
Unit: in (mm)
Pipe size
Model MMD-
Gas side
Liquid side
AP007 to AP012
3/8" (9.5)
1/4" (6.4)
AP015 to AP018
1/2" (12.7)
1/4" (6.4)
AP021 to AP048
5/8" (15.9)
3/8" (9.5)
 Connecting refrigerant piping
Flaring
1
Cut the pipe with a pipe cutter.
Remove burrs completely. (Remaining burrs may
cause gas leakage.)
2
Insert a flare nut into the pipe, and flare the
pipe.
Use the flare nut provided with the unit or the one
used for the R410A refrigerant. The flaring
dimensions for R410A are different from the ones
used for the conventional R22 refrigerant. A new
flare tool manufactured for use with the R410A
refrigerant is recommended, but the conventional
tool can still be used if the projection margin of the
copper pipe is adjusted to be as shown in the
following table.
Projection margin in flaring: B
Unit: in (mm)
Outer dia. of
Conventional
R410A tool used
copper pipe
tool used
1/4" to 5/8"
0 to 0.02"
0.04" to 0.06"
(6.4 to 15.9)
(0 to 0.5)
(1.0 to 1.5)
Flaring diameter size: A
Unit: in (mm)
+0
Outer dia. of copper pipe
A
–0.02" (0.4)
1/4" (6.4)
0.36" (9.1)
3/8" (9.5)
0.52" (13.2)
1/2" (12.7)
0.65" (16.6)
5/8" (15.9)
0.78" (19.7)
A
* In case of flaring for R410A with the conventional
flare tool, pull it out approx. 0.02" (0.5 mm) more than
that for R22 to adjust to the specified flare size. The
copper pipe gauge is useful for adjusting projection
margin size.
• The sealed gas was sealed at the atmospheric
pressure so when the flare nut is removed, there will
no "whooshing" sound: This is normal and is not
indicative of trouble.
• Use two wrenches to connect the indoor unit pipe.
Work using double spanner
18-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents